Download Print this page
EnerSys HAWKER LifeSpeed iQ Safety And Use Instructions

EnerSys HAWKER LifeSpeed iQ Safety And Use Instructions

3-phase chargers

Advertisement

Quick Links

Safety and use instructions LifeSpeed iQ
SAFETY INSTRUCTIONS
GOALS OF THIS MANUAL
This manual is aimed at any authorized personnel wanting to
use a 3-phase LifeSpeed iQ
motive power batteries (vented, NexSys
Water Less
®
20 ranges).
This manual contains information on:
Charger functionality.
Use and setting of charger parameters.
Technical specifications of the LifeSpeed iQ chargers.
EnerSys
®
intends to provide clear and simple information
in this manual, and assumes no responsibility for misunder-
standing or improper interpretation of the information.
The owner of the equipment is required to preserve this
manual during the life of the equipment and to transfer said
manual to any subsequent purchaser.
WARRANTY
Warranty is offered by the
regulations. Please contact your local distributor for further
information.
RECOMMENDATIONS
Recommendations for safe operation
This manual should be carefully read, prior to using the equip-
ment,
by
anyone
intending
LifeSpeed iQ:
Must not have its air circulation impaired in any way,
primarily around the air inlet areas.
Dust accumulation must be removed every 12 months.
Must be used within its protection norms, and never
be directly in contact with water.
Must be used only within the temperature range
specified in the technical specifications.
Internal connection torques must be checked once a year.
Must not be installed on a surface subject to high
vibration levels (proximity of motors, compressors, etc.).
Must not be installed close to the batteries in order to
avoid any gassing that could damage it prematurely.
Must not be installed in arduous environments such as:
• Harbour applications (saline environment)
• Close to cold stores
• External locations with exposure to wind and rain
This appliance is not intended for use by persons (including
children) with reduced physical and mental capacities, who
are not experienced in their use, unless instructed to do so by
a person responsible for their safety.
Operator safety
Take all necessary precautions when the equipment will
be used in areas where there is the possible risk of an
accident occurring. Ensure appropriate ventilation according
to standard EN 62485-3 to allow any gases released to esca-
pe. Never disconnect the battery while it is being charged.
General warnings
Requirements for use:
The equipment must be properly grounded (earthed).
The input voltage must match the charger requirements.
The
battery
voltage
capabilities.
The battery capacity is within the charger's range.
ELECTRICAL SAFETY
Safety regulations and requirements must be observed.
Safety devices installed on the electrical supply to the
chargers must be of the proper type and rating. It is
important to ensure that only fuses of the proper
capacity should be used if they need to be replaced.
The equipment must be totally disconnected from all power
sources (mains supply and battery) before it can be opened
for inspection or servicing. The battery can only be discon-
TM
- 3-phase chargers
charger to recharge lead acid
TM
®
, Gel or Water Less
manufacturer based on local
to
use
the
charger.
must
match
the
charger's
nected after the charge has been stopped by pushing the
Stop/Start button. Access to the inside of the charger should
be restricted to authorized maintenance personnel.
Please consult a qualified factory representative about any
problems or questions related to the installation of this unit.
®
/
LIMITS OF USE
This charger is designed to be used in a sheltered area.
It is designed exclusively to recharge lead batteries in an
industrial environment.
PRODUCT RECYCLING - DESTRUCTION
When this charger becomes obsolete, it can be recycled
or destroyed by authorized facilities. Local regulations will
prevail and must be followed.
MODIFICATIONS AND IMPROVEMENTS
EnerSys reserves the right, at any time, to modify or
improve its products, without any obligation to update
this product or this manual accordingly.
The customer is not permitted to modify the product from its
original design and configuration (e.g. fitting additional
modules).
Any changes made by the customer could affect the
product performance and invalidate the warranty.
RECEIVING - STORAGE
Upon receipt, please inspect visually the exterior of the
charger for any physical damage. If necessary, proceed
within 24 hours with the usual claims procedure with the
transport company.
If the charger is to be stored before use, it should remain
in the original packaging, carefully closed. Store in a clean,
dry area at a moderate temperature (0 °C to +40 °C). If the
equipment is stored at a temperature below 15°C, it must
be gradually (24 hours) restored to operating temperature
before use, to prevent the risk of condensation that could
cause electrical faults and short-circuits.
INFORMATION PLATE
Located on either side of the charger.
EU DECLARATION
EnerSys hereby declares that the chargers in the
Lifespeed iQ range covered by this declaration
conform to the descriptions laid down in:
European Directive 2014/35/EU:
Low Voltage Directive
European Standard:
EN60950-1: 2006+A11:2009+A12:2011+A1:2010+ A2:2013
European Directive 2014/30/EU:
Electromagnetic Compatibility
European Standards:
- EN61000-6-2: 2006
- EN61000-6-4: 2007+A1: 2011
European Directive 2011/65/EU:
ROHS
European Directive 2013/35/EU:
Electromagnetic fields
European Standards:
- EN62311: Oct 2008
Note: DC cables of the charger emit low power magnetic
fields in their surroundings (<5cm). Even if emissions are
below the standard limits, people bearing medical implants
should avoid operating close to the charger during recharge.
ENGLISH

Advertisement

loading
Need help?

Need help?

Do you have a question about the HAWKER LifeSpeed iQ and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for EnerSys HAWKER LifeSpeed iQ

  • Page 1 MODIFICATIONS AND IMPROVEMENTS WARRANTY EnerSys reserves the right, at any time, to modify or Warranty is offered by the manufacturer based on local improve its products, without any obligation to update regulations.
  • Page 2 DESCRIPTION & USE Navigation button Functions of the keys The keys offer the following general functions: INTRODUCTION The LifeSpeed iQ range of chargers is designed to recharge Function 24 V, 36 V, 48 V, 72V or 80 V batteries with 3-phase mains supply.
  • Page 3: Charging The Battery

    Starting the charge MODULES MANAGEMENT 1. If Autostart is ON (default), the charge starts automati- cally when the battery is connected to the charger. To • There are two types of the modules: 24/36/48V and 72/80V. stop charge, press central button •...
  • Page 4 2. If an equalisation charge has been programmed (vented battery), it will start automatically. Alternatively, an equalisation charge can be triggered manually; go to section End of charge with equalisation. 3. Press the central button or disconnect the battery that is now ready for use.
  • Page 5: Messages And Fault Codes

    Check if the Wi-iQ is pro- Fault in the air Check proper perly adjusted, circuit of the elec- operation of the pump doubt, contact EnerSys. trolyte circulation via the menu Option- system. Option test. Too high battery Verify battery temperature.