INSTALLATION

Unpacking Precautions

The unit is shipped bolted to its mounting pad, ready for
installation. Avoid damage from dropping, bumping,
collision, etc. Store and unpack carton with the proper side
up, as noted on the shipping carton.
Installing the 15A fuse could cause the engine to
start.
• Observe that the 15 Amp fuse has been removed from the
control panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.

Delivery Inspection

After removing the carton, carefully inspect the Home
Generator System for any damage that may have occurred
during shipment.
IMPORTANT: If loss or damage is noted at time of delivery,
have the person(s) making delivery note all damage on the
freight bill and affix his signature under the consignor's
memo of loss or damage. If loss or damage is noted after
delivery, separate the damaged materials and contact the
carrier for claim procedures. Missing or damaged parts are
not warranted.

Shipment Contents

The Home Generator System is supplied with:
• Home Generator System
• Pre-attached mounting pad
• One flexible hook-up hose
• This installation and start-up manual
• Operator's manual
• Illustrated parts list manual
• Installation checklist
• Two access door keys
• Four lifting hole plugs
• Oil fill spout
• One spare 15A fuse
• 2 Pole connector - 240V from house
• 10 Pole connector - Sensing and control wires
• Air intake engine cover
• Alternator cover
• Diagnostic LED kit (red LED/plate/screws (2))
CAUTION
INSTALLATION

Required Specialty Tools/Equipment

• Two 48" lengths of 1" pipe (NOT conduit)
• Hole punches for 16ga steel
• Torque screwdriver, 5 to 50 inch-pound range

Home Generator System Location

Before installing generator, consult with homeowner and convey
the following guidelines which may affect the desired location.
Exhaust heat/gases can ignite combustibles or
structures causing a fire.
• DO NOT install the generator closer than 5 feet (1.5m) from
any combustibles or structures with combustible walls having
a fire resistance rating of less than 1 hour.
• Keep at least 3 ft. (91 cm) clearance on all sides of generator
including overhead.
Generator Location
Install generator outdoors in an area which will not accumulate
deadly exhaust gas. DO NOT install generator where exhaust
gas could accumulate and enter inside or be drawn into a
potentially occupied building. Ensure exhaust gas is kept away
from any windows, doors, ventilation intakes or other
openings that can allow exhaust gas to collect in a confined
area (Figure 1). Prevailing winds and air currents should be
taken into consideration when positioning generator.
Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide can cause headache,
fatigue, dizziness, vomiting, confusion, seizures,
nausea, fainting or death.
• Operate generator ONLY outdoors.
• Install a battery operated carbon monoxide alarm near the
bedrooms.
• Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes, or other openings.
Figure 1 — Home Generator System Location
6
WARNING
WARNING
Exhaust Port

Advertisement