Briggs & Stratton 40204 Installation And Start-Up Manual page 17

12000 / 15000 home generator system
Hide thumbs Also See for 40204:
Table of Contents

Advertisement

Available languages

Available languages

3.
Connect an accurate frequency meter to the line side of
the generator's main circuit breaker.
4.
Ensure that the 15 Amp fuse is installed.
5.
Set the generator's main circuit breaker ON.
6.
Set the generator's system switch to AUTO.
7. Push MANUAL OVER-RIDE switch on control panel.
When the engine starts, allow it to warm up for five
minutes.
8A. For a 12kW generator, normal no load frequency is 62.0
to 62.5 Hz. If adjustment is needed at no load, slowly
rotate the governor adjustment nut (Figure 15) clockwise
and/or counterclockwise until frequency is 62.0 to
62.5 Hz.
Figure 15 — Governor Adjustment Nut
Governor
Adjustment Nut
8B. For a 15kW generator, normal no load frequency is 62.0
to 62.5 Hz. If adjustment is needed at no load, slowly
rotate the governor adjustment screw (Figure 16)
clockwise and/or counterclockwise until frequency is
62.0 to 62.5 Hz.
Figure 16 — Governor Adjustment Screw
Governor
Adjustment
Screw
INSTALLATION
9.
Push and hold MANUAL OVER-RIDE switch on control
panel again until engine stops.
10. Turn the service disconnect to the transfer switch off.
After a short time delay, the transfer switch will connect
to the generator.
11. Load generator to full load.
12. Connect an accurate frequency meter to the load side of
the generator's main circuit breaker. Frequency should
be above 57.0 Hz.
13. If frequency is below 57.0 Hz, slowly rotate the governor
adjustment nut or screw clockwise and/or
counterclockwise until frequency is above 57.0 Hz.
14. Turn the service disconnect to the transfer switch on.
The transfer switch will connect to the utility after five
minutes.
15. After the engine has stopped running,
If an adjustment was made in step 13, repeat steps
3 through 9.
If an adjustment was not made in step 13, proceed
to step 16.
IMPORTANT: If the no load frequency falls out of the no load
parameter after full load adjustment is made, contact an
authorized service center.
16. Reinstall the circuit breaker cover to the air intake guard.
17. Close the oil drain and control panel access doors.