• Tank disinfection setting 1, 2

Disinfection operation is special DHW tank operation mode to kill and to prevent growth of viruses inside the tank.
- Disinfection active : Selecting enable or disable of disinfection operation.
- Start date : Determining the date when the disinfection mode is running.
- Start time : Determining the time when the disinfection mode is running.
- Max temp. : Target temperature of disinfection mode.
- Duration time : Duration of disinfection mode.

Vales of Tank disinfection setting

• If Disinfection active is set as ' Not use', that is 'disable disinfection mode', Start date and Start time is not
used.
• When Disinfection active is set as 'Use', that is 'enable disinfection mode', Start date is displayed at the posi-
tion of Disinfection active and Start time is displayed at the position of Start date.

DHW heating should be enable.

• If DHW heating is disable, the disinfection mode will not be operated although Disinfection active is set as
'Use'.
• To use disinfection mode, DHW heating should be enable. (by button input or scheduler programming)
Water temperature
(Inside DHW tank)
Max temp
Start time
Temperature profile
of Disinfection operation
Duration time
Time