For CS-A18MKD, CS-A24MKD and CS-A28MKD

12.8 Horizontal Airflow Direction Control

12.8.1 Auto Control
When the horizontal airflow direction is set to Auto using the remote control, the vanes swings left and right as
shown in the diagram.
When stopped with remote control, the discharge vane is reset, and stop at the reset position.
During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that
condition, the vane will stop swinging and rest at face front position.
During Heating operation, the piping air temperature reaches 38°C, the vanes swings left and right. When the
piping air temperature falls to 35°C, the vanes will stop swing and rest at face front position.
For CS-A9MK and CS-A12MK
12.8.2
Manual Control
When the horizontal airflow direction is set to Manual using the remote control, the automatic airflow is released
and the airflow direction vane move left and right in the range shown in the diagram.
The louver can be adjusted by pressing the button to the desired vane position.
When stopped with remote control, the vanes is reset and stopped at reset position.
For CS- A9MK and CS-A12MK
Airflow Direction Patterns of Remote Control
For CS-A18MK, CS-A24MK and CS-A28MK
Airflow Direction Patterns of Remote Control
Closing
position
/ 148°
Pattern
Vane Angle (°)
Pattern
Vane Angle (°)
Horizontal
17°
Upper limit for
heating mode
27°
33°
42°
52°
Lower limit for heating mode
For CS-A18MK, CS-A24MK and CS-A28MK
1
2
30°
60°
45°
1
2
26°
52°
39°
62
3
4
5
15°
3
4
5
13°