1. Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. • Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. •...
Page 4
WARNING 20. After completion of installation or service, confirm there is no leakage or refrigerant gas. It may generate toxic gas when the refrigerant contacts with fire. 21. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts with fire. 22.
2. Specification Indoor CS-A9KKD CS-A12KKD Model Outdoor CU-A9KKD CU-A12KKD Performance Test Condition NEW JIS NEW JIS Phase, Hz Single, 50 Single, 50 Power Supply 2.65 2.65 3.52 3.54 Capacity BTU/h 9040 9040 12000 12100 Kcal/h 2280 2280 3030 3040 Running Current Input Power 1.08k...
Page 6
Type Propeller Fan Propeller Fan Material PP Resin PP Resin Motor Type Induction (6 poles) Induction (6 poles) Input Power 55.6 - 63.1 65 - 73 Output Power Speed 800 - 830 835 - 845 Moisture Removal L/h (Pt/h) 1.6 (3.4) 2.0 (4.2) Cooling: 7.4 (263) - 7.4 (263) Cooling: 7.9 (277) - 7.9 (277)
Page 7
Maximum Cooling Outdoor Minimum Operation Maximum Range Heating Minimum Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb) Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb) Specifications are subjected to change without prior notice for further improvement.
Page 8
Indoor CS-A18KKD CS-A24KKD Model Outdoor CU-A18KKD CU-A24KKD Performance Test Condition NEW JIS NEW JIS Phase, Hz Single, 50 Single, 50 Power Supply 5.30 5.30 7.03 7.03 Capacity BTU/h 18100 18100 24000 24000 Running Current 12.3 12.2 Input Power 1.72k 1.76k 2.54k 2.58k 3.08...
Page 10
Indoor CS-A28KKD Model Outdoor CU-A28KKD Performance Test Condition NEW JIS Phase, Hz Single, 50 Power Supply 8.00 8.00 Capacity BTU/h 27300 27300 kJ/h 28800 28800 Running Current 13.2 12.7 Input Power 2.86k 2.88k 2.80 2.78 Btu/hW 9.55 9.48 Power Factor dB-A 49 / 44 Indoor Noise (H / L)
Page 11
Type Propeller Fan Material Motor Type Induction (8 poles) Input Power 146.7 - 154.9 Output Power 460 - 490 Speed 840 - 855 Moisture Removal L/h (Pt/h) 4.7 (9.9) Cooling: 16.5 (583) - 16.5 (583) /min (ft /min) Heating: 17.6 (622) - 17.6 (622) Cooling: 18.2 (643) - 18.2 (643) /min (ft /min)
Page 12
Maximum Cooling Outdoor Minimum Operation Maximum Range Heating Minimum Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb) Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb) Specifications are subjected to change without prior notice for further improvement.
Features • E-ion Air Purifying System with Patrol Sensor Active e-ions are released to catch dust particles and bring them back the large positively charged filter. Patrol Sensor color changes to indicate the dirt level in the air • Long Installation Piping CS/CU-A9KK, long piping up to 10 meters.
8. Wiring Connection Diagram CS-A9KKD CU-A9KKD Resistance of Indoor Fan Motor Windings Resistance of Compressor Windings MODEL CS-A9KKD MODEL CU-A9KKD CONNECTION CWA921409 CONNECTION 2PS156D3DA02 BLUE-YELLOW 457.2Ω 4.228Ω YELLOW-RED 420.5Ω 3.841Ω Note: Resistance at 20°C of ambient temperature. Note: Resistance at 20°C of ambient temperature.
CS-A12KKD CU-A12KKD Resistance of Indoor Fan Motor Windings Resistance of Compressor Windings MODEL CS-A12KKD MODEL CU-A12KKD CONNECTION CWA921415 CONNECTION 2PS206D2BA02 BLUE-YELLOW 196Ω 3.207Ω YELLOW-RED 303Ω 3.256Ω Note: Resistance at 20°C of ambient temperature. Note: Resistance at 20°C of ambient temperature. Resistance of Outdoor Fan Motor Windings MODEL CU-A12KKD...
CS-A28KKD CU-A28KKD Resistance of Outdoor Fan Motor Windings Resistance of Compressor Windings MODEL CU-A28KKD MODEL CU-A28KKD CONNECTION CWA951294J CONNECTION 2JD514E3AA03 BLUE-YELLOW 102Ω 1.022Ω YELLOW-ORANGE 81Ω 2.142Ω YELLOW-RED 108Ω Note: Resistance at 20°C of ambient temperature. Note: Resistance at 25°C of ambient temperature.
11.1.3 Indoor/Outdoor Unit Installation 11. Installation Instruction Diagram 11.1 Select the Best Location 11.1.1 Indoor Unit • Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. • There should not be any heat source or steam near the unit.
11.2 Indoor Unit 11.2.1 How to Fix Installation Plate The mounting wall is strong and solid enough to prevent if from the vibration. The centre of installation plate should be at more than at right and left of the wall. The distance from installation plate edge to ceiling should more than From installation plate left edge to unit’s left side is From installation plate right edge to unit’s right side is...
Page 39
11.2.3 Indoor Unit Installation Caution Use shock absorber during pull out the piping to protect the intake grille Do not turn over the unit without it ’s shock from damage. absorber during pull out the piping. It may cause intake grille damage Piping Piping Shock absorber...
Page 40
11.2.4 Connect the Cable to the Indoor Unit The inside and outside connecting cable can be connected without removing the front grille. a) INDOOR POWER SUPPLY MODEL (1.0 ~ 2.5HP) Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 x 1.5mm (1.0~1.5HP) or 5 x 2.5mm (2.0~2.5HP)
Page 41
b) OUTDOOR POWER SUPPLY MODEL (3.0HP) Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 6 x 1.5mm (3.0HP) flexible cord, type designation 245 IEC 57 or heavier cord. • Secure the connecting cable onto the control board with the holder.
11.3 Outdoor Unit 11.3.1 Install the Outdoor Unit • After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
Page 43
11.3.3 Evacuation of the Equipment Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve. Be sure to connect the end of the charging hose with the push pin to the service port. Connect the center hose of the charging set to a vacuum pump.
Page 44
11.3.4 Connect the cable to the Outdoor Unit a) INDOOR POWER SUPPLY MODEL (1.0~2.5HP) Remove the control board cover from the unit by loosening the screw. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 x 1.5mm (1.0~1.5HP) or 5 x 2.5mm (2.0~2.5HP) flexible cord, type designation 245 IEC 57 or...
Page 45
11.3.5 Pipe Insulation Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E-FOAM with thickness 6mm or above.
The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C. • During heating operation, the compressor will stop running and restart as shown in below figure. (A9/12KK) (A18/24/28KK) 12.1.1 Heating Operation Time Diagram (For CS-A9KKD CU-A9KKD and CS-A12KKD CU- A12KKD)
Page 47
12.1.2 Heating Operation Time Diagram (For CS-A18KKD CU-A18KKD, CS-A24KKD CU-A24KKD and CS-A28KKD CU-A28KKD)
The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C. • During cooling operation, the compressor will stop and restart as shown in figure below: 12.2.1 Cooling Operation Time Diagram (For CS-A9KKD CU-A9KKD and CS-A12KKD CU-A12KKD)
Page 49
12.2.2 Cooling Operation Time Diagram (For CS-A18KKD CU-A18KKD, CS-A24KKD CU-A24KKD and CS-A28KKD CU-A28KKD)
However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point. 12.3.1 Soft Dry Operation Time Diagram (For CS-A9KKD CU-A9KKD and CS-A12KKD CU- A12KKD)
Page 51
12.3.2 Soft Dry Operation Time Diagram (For CS-A18KKD CU-A18KKD, CS-A24KKD CU-A24KKD and CS-A28KKD CU-A28KKD)
12.4 Automatic Operation • Automatic operation can be set using remote control. • This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature. • After judged the temperature, the operation mode is determined by referring to the below standard. Cooling Operation ↑...
JX03 at indoor unit’s printed circuit board. 12.5 Indoor Fan Speed Control • Indoor fan speed can be set using remote control. 12.5.1 Fan Speed Rotation Chart Fan Speed (rpm) CS-A9KKD CS-A12KKD 1080 1120 1040 1100 SSLo...
Page 54
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. Fan speed rotates in the range of Hi, Me and Lo-. Deodorizing Control will be activated. For CS-A9KKD and CS-A12KKD Speed Mode SSLo Stop...
Page 55
For CS-A18KKD, CS-A24KKD and CS-A28KKD Speed Mode SSLo Stop Manual Normal Auto Manual Powerful Auto Manual Auto Manual Normal Auto Manual Powerful Auto Auto Mode Judgment -100 Manual -100 Quiet -100 Auto -100 -100 Manual Quiet Auto -100 Manual -100 Quiet -100 Auto...
Page 56
• Auto Fan Speed during cooling operation: Indoor fan will rotate alternately between off and on as shown in below diagram. At the beginning of each compressor starts operation, indoor fan speed increases gradually for deodorizing purpose. For the first time the compressor operates, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the start of compressor.
• Auto Fan Speed during Heating operation. Indoor fan will rotate in the range of SLo → Me according to the heat exchanger temperature. (For A18KKD, A24KKD and A28KKD) (For A9KKD and A12KKD) 12.5.3 Manual Fan Speed Control • Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control. •...
• During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the louver will stop swinging. For CS-A9KKD and CS-A12KKD Horizontal Upper limit for cooling mode and soft dry mode/11°...
Page 59
The louver can be adjusted by pressing the button to the desired louver position. • When stop operation using the remote control, the discharge vent is reset, and stop at the closing position. (Cooling and Soft Dry Operation Condition) For CS-A9KKD and CS-A12KKD Horizontal Upper limit for cooling mode and 11°...
Lower limit for heating mode 12.8 Horizontal Airflow Direction Control For CS-A9KKD and CS-A12KKD, the horizontal airflow direction louver can be adjusted manually by hand. For CS-A18KKD, CS-A24KKD and CS-A28KKD the horizontal airflow direction louver are as following. 12.8.1 Auto Control •...
12.9 Powerful Operation • To achieve the setting temperature quickly. (Cooling and Soft Dry Operation condition) • When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present setting temperature (Lower temperature limit: 16°C). •...
12.10 Quiet Operation (For Cooling Operation or cooling region of Soft Dry Operation) • To provide quiet cooling operation condition. • Once the Quiet Operation is set at the remote control, the Quiet LED illuminated. The sound level will reduce around 2dB(A) for Lo fan speed or 3dB(A) for Hi/Me fan speed against the present operation sound level.
Page 63
(Heating Operation condition) • When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around 2 dB (Lo) or 3 dB (Hi, Me), against the present sound level operation. • Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
12.11 Timer Control 12.11.1 ON Timer • When the ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room will reach nearly to the set temperature by the set time. •...
12.14 Patrol Operation • To monitor air dirtiness level by using Patrol sensor and to maintain air freshness by activates e-ion operation • Patrol operation starts condition When the unit operation is started with “OFF/ON” button When the unit stops, “Patrol” operation is selected, Patrol individual operation will start. During cooling only operation, “Patrol”...
Page 66
• Patrol Sensor Control First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness level is monitored. The Air Dirtiness level is set to Clean, Patrol LED turns blue color. After that, Patrol sensor starts to record the resistance value at fixed interval. Higher resistance value indicates cleaner air.
Page 67
• Airflow direction (Horizontal, Vertical) Control During any operation mode combines with Patrol operation, airflow direction follows respective operation mode. During Patrol individual operation if e-ion starts, only Auto Air Swing is allowed. Even if “Air Swing” button is pressed, no signal is sent to air conditioner, and no change on LCD display. During Patrol individual operation if e-ion stops, Airflow direction louver closed.
Page 68
• Patrol Operation Demo Mode Patrol Operation Demo Mode start condition Press “Set” button continuously for 15 seconds by using pointer during Air Conditioner is OFF condition to enter internal setting mode. Press “Timer Decrement" button to select “Pt demo”. Press “Timer Set”...
12.15 E-ion operation • This operation provides clean air by producing negative ions to attract dust captured at the positively charged active e-ion filters. • e-ion operation start condition During unit running at any operation mode, if “e-ion” operation is selected, combination operation (operation mode + e-ion operation) starts.
Page 70
• e-ion Check Mode e-ion abnormality check mode Purpose is to improve sensor serviceability when sensor is malfunction. (1) Control starting condition When all of the conditions are formed Not in Patrol Demo mode. e-ion operation ON. When e-ion check mode signal is received; the procedure of selection is as shown: •...
Page 71
• Error Detection Control When e-ion indicator blink, it indicates error listed below: Active e-ion Air Purifying system PCB main connector open: Judgment Method • During e-ion operation (include during Patrol operation), Active e-ion Air Purifying system main connector to PCB is opened. Troubleshooting Methods •...
12.16 ECO Patrol Operation • A Pyoelectric infrared sensor is used to detect injection strength variation of infrared at setting area to determine the presence or absence of human and its activity level. Human detection area is shown in figure below: •...
Page 73
• ECO Patrol Demo Mode Press “Set” button continuously for 15 seconds by using pointer during Air Conditioner is OFF condition to enter internal setting mode. Press “Timer Decrement" button to select “EC demo”. Press “Timer Set” button to toggle ECO Patrol Demo mode. •...
Page 74
• During ECO Patrol operation, the internal setting temperature and fan speed are adjusted in order to provide comfort and energy saving. • ECO Patrol Start condition. Press ECO Patrol button to select ECO1 and ECO2. • ECO Patrol Stop condition. Press ECO Patrol button again.
Page 75
(For Cooling and Soft Dry Operation) • ECO 1 Operation High None Activity Level Temperature Set Speed Med Fan Fan Speed Set Speed +1tap Up • ECO 2 Operation Activity Level High None Temperature +1tap Up Set Speed Med Fan Fan Speed Set Speed (For Heating Operation)
Page 76
• ECO Patrol Sensor abnormality check mode • Purpose is to improve sensor serviceability when sensor is malfunction. (1) Control starting condition When all of the conditions are formed Not in ECO Patrol Demo mode. ECO Patrol mode ON. When ECO Patrol sensor check mode signal is received; the procedure of selection is as shown: •...
13. Protection Control (For A9/12KK) 13.1 Restart Control (Time Delay Safety Control) • When the thermo-off temperature (temperature which compressor stops to operate) is reached during: - Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation. Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
13.6 Compressor Reverse Rotation Protection Control • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5°C (cooling mode)/5°C (heating mode) or less for continuous 2 minutes, compressor will stop and restart automatically.
13.11 Outdoor Fan Motor Control • When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation). • This is to release the heat and to obtain the lowest pressure as fast as possible. 13.12 Hot Start Control •...
13.14 Deice Control Deice starts to prevent frosting at outdoor heat exchanger. • Normal Deice Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice operation. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (TRS CLOSE) or less for 50 sec.
Page 81
Normal Deice Time Diagram Overload Deice Time Diagram...
(For A18/24/28KK) (For 13.15 to 13.21 information applies only to Cooling and Soft Dry Operation) 13.15 Restart Control (Time Delay Safety Control) • When the thermo-off temperature (temperature which compressor stops to operate) is reached during:- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation. Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
13.20 Compressor Reverse Rotation Protection Control • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
13.24 Overload Protection Control • Outdoor Fan Control If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor Heat Exchanger temperature is Tb or more according to Outdoor Air Temperature region as table below: The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
13.27 Cold Draft Prevention Control 13.28 Deice Control Deice starts to prevent frosting at outdoor heat exchanger. • Normal Deice Deice operation detection commences in Heating operation starts or 60 minutes after previous deice operation. If the outdoor piping temperature drops to -4°C for 50 sec. continuously during compressor is in operation, deice will start.
Page 86
a) Normal Deice Time Diagram b) Overload Deice Time Diagram...
14. Servicing Mode 14.1 Auto OFF/ON Button Auto OFF/ON Auto OFF/ON Auto OFF/ON Button Pressed Button Pressed Button Pressed 5 sec 5 sec Auto Operation Test Run Operation Stop Various Setting Mode Stop (Forced Cooling Operation) “Beep” 2 x “Beep” AUTO OPERATION MODE The Auto Operation will be activated immediately once the Auto OFF/ON button is pressed.
14.2 Remote Control Button 14.2.1 SET Button • To check current remote control transmission code and store the transmission code to EEPROM: Press “Set” button continuously for 10 seconds by using pointer. Press “Timer Set” button until a “beep” sound is heard as confirmation of transmission code change. •...
15. Troubleshooting Guide 15.1 Refrigeration cycle system In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas Pressure Outlet air Temperature Such problems include insufficient insulation, problem with the (kg/cm (°C) power source, malfunction of a compressor and a fan.
Page 90
15.1.1 Relationship between the condition of the air conditioner and pressure and electric current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant (gas leakage) Clogged capillary tube or strainer...
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 16.1 CS-A9KKD CS-A12KKD 16.1.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 16.1.1.1...
WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 16.2 CS-A18KKD CS-A24KKD CS-A28KKD 16.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 16.2.1.1...
Page 96
16.2.1.3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17...
Page 97
16.2.1.4 To remove discharge grille Figure 18 16.2.1.5 To remove control board Figure 19 16.2.1.6 To remove cross flow fan and indoor fan motor Figure 20...
18. Exploded View and Replacement Parts List 18.1 Indoor Unit 18.1.1 CS-A9KKD CS-A12KKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 121
REF. PART NAME & DESCRIPTION CS-A9KKD CS-A12KKD REMARK CHASSY COMPLETE CWD50C1653 ← FAN MOTOR CWA921409 CWA921415 CROSS FLOW FAN COMPLETE CWH02C1076 ← BEARING ASS’Y CWH64K007 ← SCREW - CROSS FLOW FAN CWH551146 ← GENERATOR COMPLETE CWH94C0028 ← EVAPORATOR CWB30C3154 CWB30C2945...
Page 122
OPERATING INSTRUCTION CWF567112 ← INSTALLATION INSTRUCTION CWF614251 ← INSTALLATION INSTRUCTION CWF614252 ← INSTALLATION INSTRUCTION CWF614255 ← COVER FOR RECEIVER (UPPER) CWD933022 ← COVER FOR RECEIVER (BOTTOM) CWD933209 ← POWER SUPPLY CORD CWA20C2827 ← INSTALLATION INSTRUCTION CWF614256 ← (Note) • All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488). •...
Page 123
18.1.2 CS-A18KKD CS-A24KKD CS-A28KKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 124
REF. NO. PART NAME & DESCRIPTION CS-A18KKD CS-A24KKD CS-A28KKD REMARK CHASSY COMPLETE CWD50C1654 ← ← FAN MOTOR L6CBYYYL0037 L6CBYYYL0039 ← CROSS FLOW FAN COMPLETE CWH02C1077 ← ← BEARING ASS’Y CWH64K007 ← ← SCREW - CROSS FLOW FAN CWH551146 ← ← ION GENERATOR CWH94C0028 ←...
18.2 Outdoor Unit 18.2.1 CU-A9KKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 127
REF. PART NAME & DESCRIPTION CU-A9KKD REMARK CHASSY ASS’Y CWD50K2112 SOUND PROOF MATERIAL CWG302255 FAN MOTOR BRACKET CWD541075 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR CWA951674 SCREW - FAN MOTOR MOUNT CWH55406J PROPELLER FAN ASS’Y CWH03K1020 NUT - PROPELLER FAN CWH56053J COMPRESSOR 2PS156D3DA02...
Page 128
18.2.2 CU-A12KKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 129
REF. PART NAME & DESCRIPTION CU-A12KKD REMARK CHASSY ASS’Y CWD50K2074 SOUND PROOF MATERIAL CWG302110 FAN MOTOR BRACKET CWD541030 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR CWA951121J SCREW - FAN MOTOR MOUNT CWH55406J PROPELLER FAN ASS’Y CWH03K1006 NUT - PROPELLER FAN CWH56053J COMPRESSOR 2PS206D2BA02...
Page 130
18.2.3 CU-A18KKD CU-A24KKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 131
REF. NO. PART NAME & DESCRIPTION CU-A18KKD CU-A24KKD REMARK CHASSY ASS’Y CWD50K2087 ← COMPRESSOR 2JS318D3AA04 2JS438D3JA02 ANTI - VIBRATION BUSHING CWH50055 ← NUT - COMPRESSOR MOUNT CWH561049 ← PACKING CWB81043 ← CONDENSER CWB32C2678 CWB32C2679 SOUND PROOF BOARD CWH151051 ← FAN MOTOR BRACKET CWD541055 ←...
Page 132
18.2.4 CU-A28KKD Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 133
REF. PART NAME & DESCRIPTION CU-A28KKD REMARK CHASSY ASSY CWD50K2087 COMPRESSOR 2JD514E3AA03 ANTI-VIBRATION BUSHING CWH50055 NUT-COMPRESSOR MOUNT CWH561049 PACKING CWB81043 CONDENSER CWB32C2681 SOUND PROOF BOARD CWH151056 FAN MOTOR BRACKET CWD541055 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR CWA951294J SCREW - FAN MOTOR MOUNT CWH55252J PROPELLER FAN ASSY CWH03K1017...