Direct spraying of water on the exchanger is prohibited. When the
ramps are mounted on site, the nozzles must be oriented outwards at an
angle of 45 °, cf. diagram beside.
TROUBLESHOOTING
6-
les of faults
FAULT
Condensing Pressure too high
Condensing Pressure too low
Fans not working
PROBABLE CAUSE
Insufficient air flow into condenser.
Installation overcharged with fluid.
Air or non-condensable gas in the HP circuit.
Fan cut-in incorrectly set.
Motor out of order.
Main power lower than acceptable range.
Phase missing.
Manufactured in France by PROFROID CARRIER S. C. S
178, rue du Fauge - ZI Les Paluds - B.P. 1152 - 13782 Aubagne Cedex - France
International: Tel. (33) 4 42 18 05 00 - Fax (33) 4 42 18 05 02
ACTION REQUIRED
Clean condenser.
Check fan motors.
Drain liquid into reservoir.
Purge
Adjust pressure switch.
Replace
Check current values with a voltmeter.
Measure current between phase and
motor terminal block.