Biddle HR 25 Manual page 57

Hide thumbs Also See for HR 25:

Advertisement

HR M
ANUAL
P
ROBLEM
The unit does not respond
to the building management
system.
The unit functions differently
from expectations.
The unit is not circulating
enough air.
The unit is making a lot of
noise.
Manual version 3.0 (10-10-2017)
P
ROBABLE CAUSE
The building management system is not
operating correctly.
The unit has no communication with
the building management system.
The unit is operating in a special mode.
One or more modules are not prop-
erly connected.
The filter(s) is/are dirty.
The fan settings are not properly cali-
brated.
The duct system is giving too much
resistance.
An air damper is not working properly.
The connected ventilation unit is not
working properly.
The filter(s) is/are dirty.
A component is loose.
See also:
2.7
"Connecting the unit to the building management system"
on page 21
2.12 Switching on and checking operation op pagina 27
6.2
"Replacing or cleaning the filter" on page 58
W
HAT TO DO
Check the building management sys-
tem.
• Check the building management
system.
• Check the wiring.
• If necessary, set the unit to emit a
signal without adjusting the opera-
tion (register address 337).
• Check the connections of the
modules
• Check the operation of the unit.
(See
2.12.5 Checking operation
Clean or replace filter(s).
Calibrate the fan settings properly. see
2.12.4> Setting the fan speeds
Resolve problems in the duct system:
• ducts too narrow
• bends too sharp
• blockages
Check the operation of the damper
(See
2.12.5 Checking
operation).
Check the operation of the connected
units.
Clean or replace filter(s).
Check the unit:
• are the inspection doors closed?
• are the rubber seals still in good
condition?
en
E
RRORS
)
en-57