HR M
ANUAL
5.2
Remedying errors that are accompanied by an error message
E
RROR MESSAGE
The malfunction lamp is lit up.
5.3
Reading out errors
5.4
Error codes registers
B
V
IT
ALUE
3
8
12
4096
E
F-
RROR
[1];
LAGS
M
217
ODBUS
B
V
IT
ALUE
0
1
14
8192
...
...
Manual version 3.0 (10-10-2017)
P
ROBABLE CAUSE
The filter is letting insufficient air
through, due to contamination.
See also:
6.2
"Replacing or cleaning the filter" on page 58
Errors are recorded with a binary code in two registers.
In the log file "log_error.csv", which can be read out with a
USB flash drive, the errors are indicated with a numeric value.
Error codes register 216/ErrorFlags[0]
_
.
LOG
ERROR
CSV
V
C
ALUE
ODE
3
E7
12
F8
Error codes register 217/ErrorFlags[1]
L
.
OGERROR
CSV
V
C
ALUE
ODE
16
F1
29
F17
...
F18
W
HAT TO DO
Check the filter for contamination.
Clean or replace it if necessary.
You can adjust the pressure differ-
ence meter over the filter to make
it emit a dirty filter signal either
sooner or later.
D
ESCRIPTION
Fan error
Faulty pressure sensor in supply duct (X375)
D
ESCRIPTION
Filters must be replaced
Faulty CO
sensor
2
Faulty pressure sensor over extract fan (X377)
en
E
RRORS