ETC Echo Contact Input Installation Manual page 7

Table of Contents

Advertisement

ETC Installation Guide
Contact and Demand Response Interfaces
Set Space and Address / Zone Start
Interface devices participate in an Echo control system using the configured
Space and Address / Zone which are selectable using the rotary switches on
the front of the unit. By default, these switches are set to Space 1, Address /
Zone 1.
1.
Set the Space for this device (1 through 16 available). All control inputs
from the connected stations, sensors, and other controls are shared by
all devices within the selected space. This setting applies regardless of
the selected configuration mode (Basic or Custom).
Note:
determines the four consecutive spaces that will be controlled. A value
higher than 13 will result in control of only Spaces 14, 15, and 16.
2.
Set the Address / Zone:
Note:
Note:
enough in the range for all outputs in the interface. For example, if
you set the first zone to address 15, the remaining output contacts on
the controller will be assigned to and respond as Zone 16.
Contact and Demand Response Interfaces
For the Demand Response Interface, setting the Space address
For a Contact Input Interface, set the Address (1 through 16
available) which identifies the device in the selected space. This
setting always applies.
Do not duplicate a device address within the same space.
For a Contact Output Interface, set the Zone number (1 through
16 available) for the first output on the interface. The remaining
outputs will be assigned consecutive zone numbers. The zone
number does not apply while in Custom configuration mode.
When setting the first zone number, be careful to allow
Page 7 of 8