MAXinBOX 16 Plus. Multi-Function Actuator 16 outputs 16A
ZIO-MB16P
FEATURES
 8 different channels:
o
Shutter channels (up to 8).
o
Individual outputs (up to 16).
o
2-pipes Fan Coil control (up to 4 units).
 Manual output operation with push button and
LED status indicator.
 Suitable for capacitive loads, maximum 140 µF.
 Logical functions included.
 Output timing facilities.
 Total data saving on power failure.
 Size 90 x 60 x 140 mm (8 DIN units).
 DIN rail unit assembly (EN 50022), with snap fit
clamp.
 No external power supply required other than the
bus.
 KNX BCU integrated.
 Possibility to connect different phases in adjoining
outputs.
 CE directives compliant.
1. Upper outputs
2. Lower
outputs
5.Programming/Test
button
GENERAL SYSTEM SPECIFICATIONS
CONCEPT
Type of device
Voltage (typical)
Voltage range
KNX
Maximum
supply
consumption
Bus connection
External power supply
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity (relative)
Complementary characteristics
Safety class
Operation type
Device action type
Electrical solicitations period
Type of protection
Assembly
Power failure response
Response when restarting
Operation indication
Weight
PCB CTI index
Enclosure
Technical Documentation
© Zennio Avance y Tecnología S.L.
3.Programming/Test
LED
6.Output control
7.Output status LED
button
DESCRIPTION
Electric operation control device
29VDC SELV
21...31V DC
Voltage
29VDC (typical)
24VDC
Starting
Typical bus connector TP1, 0.50 mm² section
No
0ºC to +55ºC
-20ºC to +70ºC
5 to 95% RH (no condensation)
5 to 95% RH (no condensation)
Class B
II
Continuous operation
Type 1
Long
IP20, clean environment
Independent control assembly device to be mounted inside of electrical panels
with DIN rail (EN 50022).
Data saving and relay status change according to parameterization.
Data recovering and output status change according to parameterization
Programming LED indicates programming mode (red) and test mode (green).
Output status LED indicators reflect current output state.
525 gr.
175 V
PC FR V0 halogen free
Edition 1
6
2
Programming/test
programming mode. If this button is held while plugging the
device into the KNX bus, it goes into safe mode. If this button is
held more than 3 seconds, the device goes into manual mode
(test mode).
LED: programming mode indicator (red). When the device
4.KNX
goes into safe mode, it blinks (red) every half second. It lights
in green when the device is in manual mode. During start up
connector
(after reset or power failure), if the device is not in safe mode,
programming LED blinks in blue for a few seconds.
indicator
mA
11
12.5
25
Further information
MAXinBOX 16 Plus
Technical Documentation
5
3
4
Figure 1. MAXinBOX 16 Plus
button:
short
button
mW
320
300
725
www.zennio.com
1
7
press
to
set
Page 1 / 2

Advertisement

loading

Summary of Contents for Zennio MAXinBOX 16 Plus

  • Page 1 MAXinBOX 16 Plus MAXinBOX 16 Plus. Multi-Function Actuator 16 outputs 16A Technical Documentation ZIO-MB16P FEATURES  8 different channels: Shutter channels (up to 8). Individual outputs (up to 16). 2-pipes Fan Coil control (up to 4 units).  Manual output operation with push button and LED status indicator.
  • Page 2 Figure 2. Block I wiring examples (from left to right): shutter (channel A) + individual outputs (channel B), 2 shutter channels (A and B), 4 individual outputs and 2-pipe fan coil with 3-speed fan. Attaching MAXinBOX 16 Plus to DIN rail: Removing MAXinBOX 16 Plus from DIN rail: Figure 3.

This manual is also suitable for:

Zio-mb16p