ABB REL301 Instruction Manual page 99

Numerical distance relay
Hide thumbs Also See for REL301:
Table of Contents

Advertisement

I.L. 40-386.3
Setting
Software Version
Oscillographic data
Initiation
Fault data initiation
CT ratio
PT ratio
Rated frequency
CT secondary rating
Read out I and V in Primary
or secondary units
Reactance for fault location
Fault location units
Reclosing Mode
High Speed RI
RI on Zone2 trip
RI on Zone3 trip
Breaker failure reclose block
Remote pilot control
4-16
TABLE 4-1. SETTING DISPLAY (SHEET 1 OF 4)
Function Display
Front Panel
Version
Osc Data
Flt Data
CT Ratio
VT Ratio
Freq.
CT Type
Read Out
X / Dist
DistUnit
RI Type
Fast RI
Zone2 RI
Zone3 RI
RemBF RB
Pilot
Value Displayed (INCOM
numerical
Trip (TRIP) / Zone2 (Z2TR) /
Zone2, Zone3 (Z2Z3) /
∆V or ∆I (∆V∆I)
Trip (TRIP)/ Zone2 (Z2TR)/
Zone2, Zone3 (Z2Z3)
10 – 5000
30 – 7000
60 / 50 Hz
5 / 1 amps
Primary Units / Secondary Units
0.300 – 1.500 Ω/mile or /km
dependent on "DistUnit" setting
Miles / Kilometers (MI /KM)
No RI
(OFF)
φG RI
(1PR)
φφ, φG RI
(2PR)
3φ, φφ, φφG, φG RI
(3PR)
None
(NO)
Z1 / Inst I
(Z1-II)
Pilot
(PLT)
Pilot/Z1/Inst I
(ALL)
Yes / No
Yes / No
Yes / No
Yes / No
)
®
(
)
continued
(10/94)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel302

Table of Contents