ABB REL301 Instruction Manual page 100

Numerical distance relay
Hide thumbs Also See for REL301:
Table of Contents

Advertisement

Setting
System Type Selection
Forward directional ground timer
Weakfeed enable
3-Terminal line application
Blocking system channel
coordination timer
Pilot phase setting
Pilot ground setting
Pilot ground reverse reach
Zone1 phase unit
Zone1 ground unit
Zone1 ground reverse reach
Zone1 delay trip timer
Zone2 phase unit
Zone2 Phase Timer
– Timer Type
– Definite Time
– Torque Control CO Curve
(with Time Delay or Inst. Reset)
– Torque Control Pickup
– Torque Control Time Curve
Zone2 ground unit
Zone2 ground reverse reach
(
)
continued
(10/94)
TABLE 4-1. SETTING DISPLAY (SHEET 2 OF 4)
Function Display
Front Panel
SystType
FDOGTime
Weakfeed
3-Term.
Blk Time
Pilot ø
PilotG
PilotG R
Zone1 ø
Zone1G
Zone1G R
T1 Timer
Zone2 ø
T2ø Type
T2ø Time
T2ø CV
T2ø Pkup (T2PPU)
T2ø TC
Zone2 G
Zone2G R
Value Displayed (INCOM
Non Pilot
Zone1 Extension (Z1E)
POTT
PUTT
Blocking
Blocked (BLK) / 0 - 15 cycles
Yes / No
Yes / No
0 - 98 msec
Disabled (OUT) / 0.01 - 50.00Ω
Disabled (OUT) / 0.01 - 50.00Ω
Disabled (OUT) / 0.01 - 50.00Ω
Disabled (OUT) / 0.01 - 50.00Ω
Disabled (OUT) / 0.01 - 50.00Ω
Disabled (OUT) / 0.01 - 50.000Ω
0 - 15 cycles
Disabled (OUT) / 0.01 - 50.00Ω
Blocked (DISAB) / Definite Time
(DEFTM) / Torque Control (TORQ)
0.10 - 2.99 sec
CO-2/CO-5/CO-6/ CO-7/CO-8/
CO-9/ CO-11 (each w/Reset or Inst)
0.5 - 10.0 amps
(T2PTC)
1 - 63
Disabled (OUT) / 0.01 - 50.00Ω
Disabled (OUT) / 0.01 - 50.000Ω
I.L. 40-386.3
)
®
(3ZNP)
(POTT)
(PUTT)
(BLK)
4-17