ABB REL301 Instruction Manual page 102

Numerical distance relay
Hide thumbs Also See for REL301:
Table of Contents

Advertisement

Setting
Directional overcurrent ground
backup time curve family
(With Time Delay or Inst. Reset)
Ground backup pick-up
Ground backup time curves
within family
Choice of directional or non
directional ground backup
Close into fault trip
Load loss trip
Loss of potential block
Loss of current block
Trip alarm seal-in
Remote setting change enable
Real time clock set
1. Set year
2. Set month
3. Set day
4. Set weekday
5. Set hour
6. Set minute
(10/94)
TABLE 4-1. SETTING DISPLAY (SHEET4 OF 4)
Function Display
Front Panel
GB Type
GBPickup
GBTCurve
GB Dir
CIF Trip
LL Trip
LOP Blk
LOI Blk
Trip Alm
Rem. Set
Set Time
Year
Month
Day
Weekday
Hour
Minute
Value Displayed
Disabled (OUT) / CO-2 / CO-5 /
CO-6 / CO-7 / CO-8 / CO-9 / CO11
(each w/Reset or Inst.)
0.5 - 4.0 amps
1 - 63
Yes / No
CIF TRIP
CIF TRIP W/DELAY
NO CIF TRIP
Yes / No / FDOG
Yes / No
Yes / No
Seal-in (YES) or No Seal-in (NO)
Remote Allowed (YES) or
No Remote (NO)
Yes / No
1980 - 2079
1 - 12
1 - 31
Sunday (SUN) thru Saturday (SAT)
0 - 23
0 - 59
I.L. 40-386.3
(INCOM
)
®
4-19