ABB REL301 Instruction Manual page 14

Numerical distance relay
Hide thumbs Also See for REL301:
Table of Contents

Advertisement

1. 6.
SPECIFICATIONS
1.6.1
Technical
Operating Speed
(from fault detection to trip contact close (60 Hz)
ac Voltage (VLN)
ac Current (In)
Rated Frequency
Maximum Permissible ac Voltage (Thermal Rating)
• Continuous
• 10 Second
Maximum Permissible ac Current (Thermal Rating)
• Continuous
• 1 Second
Minimum Operating Current
dc Battery Voltages
Nominal
48/60 Vdc
110/125 Vdc
220/250 Vdc
dc Burdens: Battery
ac Burdens:
Voltage input
Current input
1.6.2
External Connections
Terminal blocks located on the rear of the chassis suitable for #14 square tongue lugs.
Wiring to FT-10 switches suitable for #12 wire lugs.
1.6.3
Contact Rating Data
Trip Contacts - make & carry 30 A for 1 second, 10 A continuous capability, break 50
watts resistive or 25 watts with L/R =.045 seconds. Trip contacts are:
• Trips A1, A2
• OC1
• Close-1, 2
(10/94)
12 ms (minimum)
26 ms (typical)
60 Hz 70 Vrms
50 Hz 63.5 Vrms
1 or 5 A
50 or 60 Hz
1.5 x V
Ln
2.5 x V
Ln
3 x In
100 x In
0.1 x In
Operating Range
38-70 Vdc
88-145 Vdc
176- 290 Vdc
7 W normal
30 W tripping
0.02 VA at 70 Vac/phase
0.15 VA at 5 A/phase
I.L. 40-386.3
1-7