ABB REL301 Instruction Manual page 132

Numerical distance relay
Hide thumbs Also See for REL301:
Table of Contents

Advertisement

TABLE 5-5. REL 302 SETTINGS (PILOT SYSTEM)
VERSION
X.XX
OSC Data
Trip
FLT Data
Trip
CT Ratio
1000
VT Ratio
2000
Freq
60 Hz
CT Type
5 amps
Read Out
Secondary Units
0.500 Ω/Km
X/Dist
Dist Unit
Kilometers
RI Type
No RI
Fast RI
Z1/Inst I
Zone2 RI
NO
Zone3 RI
NO
RemBF RB
NO
Pilot
NO
SystType
Non-Pilot
FDOG Time
Blocked
Weakfeed
NO
3-Term
NO
Blk Time
0 msec
Pilot ø
Disabled
Pilot G
6.00 Ohms
PilotG R
0.01 Ohms
Zone1 ø
4.50 Ohms
Zone1 G
4.50 Ohms
Zone1G R
0.01 Ohms
∅ Cycles
T1 Timer
Zone2 ø
Disabled
T2 ø Type
Definite Time
T2 ø Time
1.00 sec
Zone2 G
Disabled
Zone2G R
0.01 Ohms
NOTE:
This REL 301 settings table is for 60 Hz and 5A ct systems. For 1A ct, change
Zone1 Ø, Zone1G R, Zone2 Ø, Zone2 G, Zone2G R, Zone3 Ø, Zone3 G, Zone3G R,
OS Inner, OS Outter by multiplying a factor of 5, and all current values mentioned
in the text should be multiplied by a factor of 0.02.
(10/94)
(As Displayed on Front Panel LCD)
T2G Type
Definite Time
T2G Time
1.50 sec
Zone3 ø
Disabled
T3 ø
2.00 sec
Zone3 G
Disabled
Zone3G R
0.01 Ohms
T3 G
2.50 sec
Zone3
Forward Dir
Ang Pos.
75°
Ang Zero
75°
Z0L/Z1L
3.0
Low V
60 Volts
Low Iø
0.50 amps
IM
0.50 amps
3IOs
0.50 amps
3IOm
0.50 amps
Inst. ø
Disabled
Inst. G
Disabled
OS Block
NO
OSOT
4000 sec
OS Inner
15.00 Ohms
OS Outer
15.00 Ohms
Dir Type
Zero Sequence
GB Type
Disabled
GB Pickup
0.50 amps
GBT Curve
24
GB Dir
YES
CIF Trip
NO
LL Trip
NO
LOP Blk
NO
LOI Blk
NO
Trip Alm
Seal-in
Rem. Set
Remote Allowed
Set Time
NO
I.L. 40-386.3
5-25