ABB REL301 Instruction Manual page 101

Numerical distance relay
Hide thumbs Also See for REL301:
Table of Contents

Advertisement

I.L. 40-386.3
Setting
Zone2 Ground Timer
– Timer Type
– Definite Time
– Torque Control CO Curve
(with Time Delay or Inst. Reset)
– Torque Control Pickup
– Torque Control Time Curve
Zone3 phase unit
Zone3 phase timer
Zone3 ground unit
Zone3 ground reverse reach
Zone3 ground timer
Zone3 direction
Pos. seq. line impedance angle
Zero seq. line impedance angle
Z0L / Z1L
Low voltage unit
Overcurrent units:
– Low set phase
– Medium set phase
– Low set ground
– Medium set ground
– High set phase
– High set ground
Out-of-step block
OSB override timer
OSB inner blinder
OSB outer blinder
Directional Unit Polarization
4-18
TABLE 4-1. SETTING DISPLAY (SHEET 3 OF 4)
Function Display
Front Panel
T2G Type
T2GTime
T2GCV
T2G Pkup (T2GPU
T2G TC
Zone3 ø
T3 ø
Zone3 G
Zone3G R
T3 G
Zone3
Ang Pos.
Ang Zero
Z0L/Z1L
Low V
Low Iø
IM
3I0s
3I0m
Inst. ø
Inst. G
OS Block
OSOT
OS Inner
OS Outer
Dir Type
Value Displayed
Blocked (DISAB) / Definite Time
(DEFTM) / Torque Control (TORQ)
0.10 - 2.99 sec
CO-2/CO-5/CO-6/ CO-7/CO-8/
CO-9/ CO-11 Reset or Instantaneous
0.5 - 10.0 amps
(T2GTC)
1 - 63
Disabled (OUT) / 0.01 -50.00Ω
Blocked (BLK) / 0.10 - 9.99 sec
Disabled (OUT) / 0.01 - 50.00 Ω
Disable (OUT) / 0.01 - 50.00Ω
Blocked (BLK) / 0.10 - 9.99 sec
Forward dir.
Reverse dir.
10 - 90 degrees
10 - 90 degrees
0.1 - 10.0
40 - 60 Volts
0.5 - 10.0 amps
0.5 - 10.0 amps
0.5 - 10.0 amps
0.5 - 10.0 amps
Disabled (OUT) / 2 - 150 amps
Disabled (OUT) / 2- 150 amps
Yes / No
400 - 4000 msec
1.0 - 15.0Ω
3.0 - 15.0Ω
Zero sequence
Negative sequ
Dual Polariz
(INCOM
)
®
(FWD)
(REV)
(rms)
(ZSEQ)
(NSEQ)
(DUAL)
(
)
continued
(10/94)