Atu Fault / Acoustic Fault / Fpe Fault - Honeywell ESSER Fire Alarm Control Panel Compact Commissioning Instruction

Table of Contents

Advertisement

9.3

ATU fault / Acoustic fault / FPE fault

The example shows an ATU fault. Acoustic and FPE faults are shown similarly.
1. trouble control:0005
alarm MB
wire break
code entry
code:
****
Code
main menu
1 information
2 overview
3 operate
4 enter access level 3
2
3
DEF
operate
1 zone/detector
2 control zone
3 primary loop
2
2
ABC
control zone
1 number
:
<-0001->
2 on
3 off
- activation
state
: idle
text 1
: ATU
2
text 2
: Out_1 mainboard
1
control
control :
+0001+
control zone 1
2
5
JKL
control zone
1 control zone
:
<-0003->
2 on
3 off
- activation
state
: wire break
text 1 : sounder
2
text 2 : Out_1 mainboard
4
GHI
control zone
1 number :
<-0003->
2 on
3 off
- activation
state
: idle
text 1 : sounder
2
text 2 : Out_1 mainboard
Fig. 66: ATU fault (example)
FIP/FOP fault
A FIP / FOP (Fire Brigade Indicating Panel / Fire Brigade Operating Panel) is displayed according
to the event. The fault warning is only displayed if the fault cause exists.
FB 798238.GB0 / 10.14
14:45
12.08
ATU fault warning
Enter access code
Main menu
2
Operate
2
Control zone
2
Select control zone
2
Correct fault
2
After correcting the fault, switch on the control
the status again.
2
Fire Alarm Control Panel Compact
and check
2
A B C
45