If system input was selected:
type
1 fire
2 techn. alarm
3 pre-alarm
4 fault
5 control input
6 system input
7 unused
function
1 ATU active
2 ATU fault
3 FPI activated
4 FPI fault
5 ESI activated
6 ESI fault
7 sound activated
function
1 sound fault
2 activate revision
3 activate access level 2
4 start verification
5 buzzer off
6 panel reset
7 lamp test
function
1 none
Fig. 29 : >System input< menu screens
5.4.2 Latching
This setting relates to the triggering of the zone and can be switched between ON or OFF
predefined via the "Fire" type.
zone <-0021->
1 type
:
control input
2 hardware
:
IN_1
3 latched
:
off
4 crtl. funct.
:
2 coming / 3 going
5 label 1 : [ATU activated
6 label 2 : [IN_1 Mainboard
3
Fig. 30 : >Latching< menu screen
FB 798238.GB0 / 10.14
3
6
MNO
3
3
3
]
]
3
Fire Alarm Control Panel Compact
unless already
19