6.4.1 Language selection
The language for the system text shown in the display can be selected in this menu.
settings
1 display functions
2 system timings
3 switching timings
4 language
3
4
language selection
1 German
2 English
3 France
4 Netherlands
3
Fig. 59: >Language selection< menu screens
7

Verify and save

The data record is verified before it is saved. Detailed warning and error messages will be displayed in the case
of an incorrect or invalid configuration and the cause(s) must be corrected before the data record can be saved.
Only a correct data record without warnings can be saved as the current data record.
configuration
1 zones
2 control zones
- detector/transponder
4 configuration
5 settings
6 verify and save
3
6
verify and safe
1 warnings
:
1
2 fault
:
2
save
4 cancel
3
2
warning
1 zone 0008 MZD to unused zone
3
Fig. 60:: >Verify and save< menu screens
FB 798238.GB0 / 10.14
Select language menu item with the
3
GHI
Select the desired language with the digit keys.
ESC  exit sub-menu
3
Select the verify and save menu item with the
3
MNO
Display of warnings (1) and faults (2).
Details are displayed in the relating sub-menu.
The >save< function can only be selected when warnings or
faults are no longer displayed and a correct data record exists.
3
Example:
ABC
The detector zone 8 was programmed with 2-zone dependency.
The assigned second detector zone is not available (e.g. configured
as >unused<).
Pressing the
for zone 0008.
3
Fire Alarm Control Panel Compact
4
GHI
1
key will take you directly to the editing menu
key.
6
key.
MNO