Toshiba MMW-UP0271LQ-E Installation Manual page 39

Hot water module (multi type)
Hide thumbs Also See for MMW-UP0271LQ-E:
Table of Contents

Advertisement

Wired remote
controller display
01: Comp. 1 side
P26
P26
02: Comp. 2 side
03: Comp. 3 side
01: Comp. 1 side
P29
P29
02: Comp. 2 side
03: Comp. 3 side
P31
A01
A01
Detected Hot water module address
A02
A02
Detected Hot water module address
A04
A04
Detected Hot water module address
*1 Inverter quantity information
(Super Modular Multi System i series (SMMS-i))
Comp. Inverter
Fan
No.
Inverter
1
2
3
01
Comp. 1
02
Comp. 2
03
Comp. 1 + Comp. 2
04
Comp. 3
05
Comp. 1 + Comp. 3
06
Comp. 2 + Comp. 3
07
Comp. 1 + Comp. 2 + Comp. 3
08
Fan
09
Comp. 1 + Fan
0A
Comp. 2 + Fan
0B
Comp. 1 + Comp. 2 + Fan
0C
Comp. 3 + Fan
0D
Comp. 1 + Comp. 3 + Fan
0E
Comp. 2 + Comp. 3 + Fan
0F
All
: Inverter trouble
Trouble detected by central control device
Central control device
indication
C05
C06
C12
Differs according to trouble contents of unit with occurrence of alarm
P30
75-EN
Check code
Outdoor unit 7-segment display
Auxiliary code
1 : Comp. 1 side
2 : Comp. 2 side
1 : Comp. 1 side
2 : Comp. 2 side
*1 Inverter quantity information
(Super Modular Multi System e and u series (SMMS-e, SMMS-u))
Trouble
No.
01
02
03
08
09
0A
0B
10
11
12
13
18
19
1A
1B
Check code
Outdoor unit 7-segment display
Auxiliary code
IPM short protection trouble
Comp. position detective circuit system trouble
Other indoor unit trouble
(Group follower indoor unit trouble)
Flow switch operation trouble
Water temperature decrease trouble
Activation of water heat exchanger frost protection
Fan
Comp. Inverter
Inverter
Trouble
1
2
1
2
Comp. 1
Comp. 2
Comp. 1 + Comp. 2
Fan1
Comp. 1 + Fan1
Comp. 2 + Fan1
Comp. 1 + Comp. 2 + Fan1
Fan2
Comp. 1 + Fan2
Comp. 2 + Fan2
Comp. 1 + Comp. 2 + Fan2
Fan1 + Fan2
Comp. 1 + Fan1 + Fan2
Comp. 2 + Fan1 + Fan2
All
: Inverter trouble
Sending trouble in central control device
Receiving trouble in central control device
Batch alarm of general-purpose equipment control interface
Group control follower unit trouble
Duplication addresses of indoor units in central control device
– 38 –
Check code name
• For details about check codes determined with an Interface
P.C board or an Inverter P.C board, refer to the Installation
Manual of the outdoor unit.
• For details about check codes of MiNi SMMS (MCY), refer to
the Installation Manual of the outdoor unit.
Check code name
Judging device
Compressor inverter
Compressor inverter
Indoor unit
Hot water module
Hot water module
Hot water module
Judging device
Central control device
Central control device
General-purpose equipment I/F
Central control device
76-EN