GLEB Kitchen exhaust fan 1 Important Information Fläkt Woods GLEB kitchen exhaust fan HT-versions comply with the requirements for EN 12101-3 standard and health and safety of the EC Machinery Directive. All fans leave the factory after being subjected to testing.
Page 5
GLEB Kitchen exhaust fan 3.3 Fan and motor range Max. speed Motor power Voltage Current Max. frequency Fan code Motor code Motor IEC [rpm] [kW] [H z] GLEB-1-025-3-037-0 APAL-2-00037-1-2-6 2900 0,37 3x230/3x400 1,68/0,97 51,8 GLEB-1-031-3-055-0 APAL-4-00055-1-2-6 2200 0,55 3x230/3x400 2,74/1,58...
GLEB Kitchen exhaust fan 4 Transport 4.1 Transport inspection Check the fan immediately after you receive it and make sure that it has not been damaged during transport. If you discover any damage, get in touch with the transportation company without delay.
GLEB Kitchen exhaust fan 5 Mounting Instructions 5.1 Installation of the fan The fan is secured to a base by M8 pin bolts and nuts (4 pcs) in mounting holes across anti- vibration mountings, included in delivery (see 3.1 Design, part 5). The base must be level and stable.
Page 8
GLEB Kitchen exhaust fan 5.4 Electrical connections All electrical connections must be wired by authorised personnel only. The necessary electrical and safety precautions must be taken into account. If the motor is operated across a frequency converter, the connections must be made according to the instructions of the frequency converter manufacturer.
GLEB Kitchen exhaust fan 6 Commissioning 6.1 Safety checking Open the cleaning hatch (see 3.1 Design, part 9) and rotate the shaft to check that the impeller can move freely. Make sure that there are no foreign objects in the fan or in the ducting. Also check that there is no unusual noise in the fan.
Page 10
GLEB Kitchen exhaust fan 7.2.2 Inspection intervals Inspection intervals can be defined by local authorities. If nothing else is mentioned, the fan shall be tested according to the intervals in table, but at least once a year. The annual inspection must be done by authorized persons only.
Page 11
GLEB Kitchen exhaust fan 7.2.3 Checking the motor bearings If the standard fan is used also in the normal ventilation, after 40000 hours of operation the fan is to be checked twice a year (motor exchange is recommended). For HT-version of the fan, it is recommended to change the motor every three years.
Page 12
GLEB Kitchen exhaust fan 7.3 Replacing the motor The fan has to be disconnected from the duct system and mains before the motor can be replaced. 1. Check that the motor is disconnected from mains. 2. Open the cleaning hathc(es).
Page 13
GLEB Kitchen exhaust fan 7.5 Final inspection Check that: The overlap between the impeller and the inlet cone is same as before maintenance. The inlet cone is aligned precisely with the impeller. All screws and nuts have been tightened. Fire-resistant sealing in the casing is ok.
GLEB Kitchen exhaust fan 8. Scrapping Materials used in fan are listed below. Disposing of those materials should be done according to valid instructions. Component Material Standing skids Steel Vibration dampers (rubber) Rubber Fan casing Steel Motor bracket Steel Noise isolation...
GLEB Kitchen exhaust fan 11. Code key Kitchen exhaust fan GLEB- a- bbb- c- ddd- e Environment (a) 1= Normal 6= Smoke extraction Fan size (bbb) 025, 031, 040, 050 Motor type (c) 1= 1-phase 3= 3-phase Motor power (ddd) 055= 0,55 kW etc.