Indoor Fan Motor Test Procedure; Testing Temperature Sensors - Haier 2U18MS2VHB Service Manual

Ductless multi-split heat pump, outdoor/indoor, wall mount - highwall, 2'x2' compact cassette, 3'x3' large cassette, slim duct, mid-static ducted, medium static ducted, console
Hide thumbs Also See for 2U18MS2VHB:
Table of Contents

Advertisement

Indoor Fan Motor Test Procedure

If the indoor fan motor does not run:
1. Disconnect power to the system.
2. Remove the return air cover and access the circuit board fan motor connection.
3. Reset power and turn the remote control fan command to Fan On mode.
Motor Test:
1. If the motor doesn't run, check for 310VDC between Pins 1 and 3. If it is
not present, the indoor board is bad. If voltage is present, continue on.
2. Check the voltage between Pins 3 and 4. The voltage should be +15VDC.
If it is not present, the board is bad. If voltage is present, continue on.
3. Check for voltage between Pins 3 and 6. If no DC voltage is present, the
board is bad. If voltage is present, change the motor.

Testing Temperature Sensors

The easiest problems to solve will involve codes that are related to potential failure of temperature sensors. Common problems
may include loose connections, open electrically, and out of calibration. Checking the condition of the sensors requires a
temperature probe and an ohmmeter.
The Reference Section of this manual contains temperature resistance tables that can be used to check the calibration of the
sensors. The measured resistance must be within the tolerances printed on the top of the tables.
To test the electrical condition of a temperature sensor perform the following:
1. Confirm the sensor is firmly attached to the circuit board connection plug.
2. Remove the sensor wires form the connection plug by releasing holding tension on the plugs tension tab.
3. Use an ohmmeter to test the electrical resistance of the sensor.
4. Measure the air temperature near the sensor and compare the required resistance against measured resistance. (See chart in
reference section) If the sensor is within calibration, the sensor is good. If the sensor is out of calibration, replace the sensor.
(Tube Sensors should be removed from socket and exposed to air temperature during test.)
2
E-6
Testing
LARGE CASSETTE TECHNICAL OVERVIEW
DC Motor
4
Red
+310 VDC
Black
DC Ground
White
+15 VDC
Yellow
Signal
Blue
Feedback