1.5 SPECIFICATIONS
The UPS nameplate displays the rated kVA as well as nominal voltages and currents. The
nameplate is located on the backside of the Bypass Module door.
Table 1.3 Power Specifications
Rated output
Power
1200kVA / 1200kW
1250kVA / 1250kW
1500kVA / 1500kW
1600kVA / 1600kW
2000kVA / 2000kW
Table 1.4 UPS Cabinet Information
UPS
Cable
[kVA]
Entry
1200 BOTTOM / TOP 133.9 / 3400
1250 BOTTOM / TOP 133.9 / 3400
1500 BOTTOM / TOP 169.3 / 4300
1600 BOTTOM / TOP 169.3 / 4300
2000 BOTTOM / TOP 192.9 / 4900
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
Input voltage
3 phase / 3 wire
480V
480V
480V
480V
480V
Width
Depth
[in / mm]
[in / mm]
35.4 / 900
35.4 / 900
35.4 / 900
35.4 / 900
35.4 / 900
MITSUBISHI ELECTRIC 9900D SERIES UPS
Bypass input voltage
3 phase / 3 wire
480V
480V
480V
480V
480V
Height
[in / mm]
80.7 / 2050
80.7 / 2050
80.7 / 2050
80.7 / 2050
80.7 / 2050
11,470 / 5220
Page Number:
1-13
Output voltage
3 phase / 3 wire
480V
480V
480V
480V
480V
Weight
Heat Loss
[lb./ kg]
[kBTU / h]
7270 / 3300
135.4
7270 / 3300
141.0
9750 / 4423
163.7
9750 / 4423
174.6
218.3