Table 7.2 Ups Module Fault Code List - Mitsubishi Electric 9900D Series Owner Technical Manual

Uninterruptible power supply system
Table of Contents

Advertisement

UPS MODULE FAULT CODES

Table 7.2 UPS Module Fault Code List

Code
indication
message
(Note 2)
MA801
I/P VOLT.OUT RNG.
MA802
I/P FREQ.OUT RNG.
MA803
I/P PHASE ABNL.
MA806
INVERTER OVERLOAD
MA807
INVERTER OVERLOAD
MA810
INVERTER OVERLOAD
MA817
EMERG.STOP ACTIV.
MA824
CB2 OPEN
MA834
BATTERY DEPLETED
MA836
INVERTER OVERLOAD
MA837
BATTERY DEPLETED2
MA860
CB1 ABNORMAL
MA861
52C ABNORMAL
MA870
BALANCER OVERLOAD
MA891
CHG. PROHIBITED
MA892
DISCHG. PROHIBITED
MA893
BATTERY ABNORMAL
MF001
I/P CIRCUIT ABL.
MF002
CONV OVERCURRENT
MF003
CONVERTER ABNL.
MF102
DC OVERVOLTAGE
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
Status
Input line voltage is out of the specified range.
(Detection Level: <78%, >116% )
Input line frequency is out of the specified range.
(Detection Level: +/-11% )
Input line power conductors are not wired in a proper
phase sequence.
The inverter output current has exceeded 105% of the
rated current.
The inverter output current has exceeded 125% of the
rated current.
Short-time over-current has been detected during the
inverter operation.
The emergency stop was activated by the EPO switch
or an external contact.
The battery circuit breaker (CB2) is open.
The battery voltage has reached the depleted level
(400V).
The UPS could not transfer to the bypass because the
bypass source has an abnormality.
The calculated battery temperature has reached the
limit level due to the long-time large discharging.
Unmatching in command and AX of CB1
Unmatching in command and AX of 52C
The UPS detected a neutral point voltage unbalance.
(Detection Level: dV>75Vdc )
CHG. PROHIBITED is activated via input port.
DISCHG. PROHIBITED is activated via input port.
BATTERY ABNORMAL is activated via input port.
Detection of a large variation of the reference error
signal.
Detection of converter overcurrent.
(Detection Level: 280%peak )
Pre-charging circuit is not working properly.
DC voltage surpasses the overvoltage level.
(Detection Level: >880Vdc )
MITSUBISHI ELECTRIC 9900D SERIES UPS
Meaning
Page Number:
7-7
External relay
contact
(Note 1)
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Major
Major
Major
Major