1.5 SPECIFICATIONS

The UPS nameplate displays the rated kVA as well as nominal voltages and currents. The
nameplate is located on the backside of the Bypass Module door.

Table 1.3 Power Specifications

Rated output
Power
1050kVA / 1000kW
1400kVA / 1330kW
1750kVA / 1660kW
2100kVA / 2000kW

Table 1.4 UPS Cabinet Information

UPS
Cable
[kVA]
Entry
1050 BOTTOM / TOP 118.2 / 3003.2
1400 BOTTOM / TOP 167.3 / 4250
1750 BOTTOM / TOP 198.8 / 5050
2100 BOTTOM / TOP 222.4 / 5650
9900CX SERIES UPS
OWNERS / TECHNICAL MANUAL
Input voltage
3 phase / 3 wire
480V
480V
480V
480V
Width
Depth
[in / mm]
[in / mm]
35.5 / 901.6
35.5 / 901.6
35.5 / 901.6
35.5 / 901.6
MITSUBISHI ELECTRIC 9900CX SERIES UPS
Bypass input voltage
3 phase / 3 wire
480V
480V
480V
480V
Height
[in / mm]
80.7 / 2048.6
80.7 / 2048.6
80.7 / 2048.6 11770/ 5350
80.7 / 2048.6 13530 / 6150
Page Number:
1-15
Output voltage
3 phase / 3 wire
480V
480V
480V
480V
Weight
Heat Loss
[lb./ kg]
[kBTU / h]
6283 / 2850
127.6
9580 / 4350
159.7
199.7
239.6