Download Print this page

External Dimension; General Specifications - Mitsubishi Electric JY992D85101A User Manual

Advertisement

2. EXTERNAL DIMENSION

2-φ4.5
(0.18)
POWER
24V+

3. GENERAL SPECIFICATIONS

Item
Operating Tempera-
ture
Storage Temperature
Operating Humidity
storage Humidity
Vibration Resistance
- Direct Mounting
Vibration Resistance
- DIN rail Mounting
Shock Resistance
Noise Immunity
Dielectric Withstand
Voltage
Insulation Resistance
Ground
PLC/power
supply
Dedicated grounding
(best)
L
N
52(2.05)
L
N
AC85 to 264V
24V+
24V-
24V+
24V-
60(2.36)
24V-
24V+
24V-
0 to 55 °C (32 to 131 °F)
-20 to 70 °C (-4 to 158 °F)
35 to 85% Relative Humidity, No condensation
35 to 90% Relative Humidity, No condensation
Conforms to JIS C0040; 10 - 57 Hz: 0.75 mm Half Amplitude
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Conforms to JIS C0040; 10 - 57 Hz: 0.035 mm Half Amplitude
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Conforms to JIS C0041: 147m/s
1000Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
500V AC > 1 min, tested between all points, terminals and ground
5MΩ > at 500V DC, tested between all points, terminals and ground
Class 3 (100 Ω or less)
Another
PLC/power
equipment
Mass: Approximately 0.3 kg
Outer color: Munsell 0.08GY/7.64/0.81
Description
57 - 150 Hz: 9.8 m/s
57 - 150 Hz: 4.9 m/s
2
Acceleration, Action Time: 11 ms
3 times in each direction X, Y, and Z
Another
supply
equipment
Common grounding
(good)
Unit:mm(inches)
DIN rail:35mm(1.38)
75(2.95)
2
Acceleration
2
Acceleration
PLC/power
supply
Common grounding
(not allowed)
Another
equipment

Advertisement