2.4 EXTERNAL SIGNAL TERMINAL BLOCK

The UPS is equipped with a series of input/output terminals for external annunciation of alarms and
for remote access of certain UPS functions. The layout of terminals is shown in Figure 2.10 with a
functional description of the input/output port presented. OUT1 to OUT8 are user programmable,
but are factory default set being also shown in Figure 2.10.
Adding same external I/F PCB "IOAU-19", doubling signal outputs is applicable for OUT1 to OUT8.

Figure 2.10(a) External Signal Terminal Block TN21-25 (NEC Class2)

TN21-25
2
4
6
8
10
12
14
16
18
20
UPS
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
1
3
5
7
9
11
13
15
17
19
*1
MITSUBISHI ELECTRIC 9900D SERIES UPS
Summary Alarm
OUT1: LOAD ON BYPASS
OUT2: LOAD ON INVERTER
OUT3: BATTERY OPERATION
OUT4: CONVERTER OPERATION
OUT5: BATTERY LOW VOLTAGE
OUT6: OVERLOAD
OUT7: SPARE
OUT8: TOTAL ALARM
52C CLOSE
*1 Relay contactor (52C close): Normally Closed