Table 3.1 List Of Ups Weights - Mitsubishi Electric 9900D Series Owner Technical Manual

Uninterruptible power supply system
Table of Contents

Advertisement

CABINET ANCHORING
All cabinets shall be securely anchored to the foundation with bolts or anchoring lugs. It is the
responsibility of the customer to size such anchoring. All mounting holes and the correct sizes of
mounting hardware and fasteners shall be used. Other means of anchoring the cabinets (e.g. welding,
adhesives, etc.) shall not be used without prior approval from Mitsubishi Electric.
CONTACT WITH FOUNDATION
The cabinet mounting shall be inspected to ensure that the cabinets are resting solidly on the
foundation by inserting a feeler gauge no thicker than 0.005 inches (0.127 mm) between the foundation
and all base channel. If the feeler gauge cannot be inserted within 2 inches of the edge of each
mounting hole, the cabinets are resting solidly on the foundation. If the feeler gauge can be inserted,
steel shims shall be inserted within 2 inches of each side of every base channel mounting hole to
maintain contact between the cabinet and foundation at all points. Refer to Figure 3.5 for shim contact
around the mounting holes on the base channel.
Figure 3.5 Shim contact around mounting holes on the base channel. (Bottom View)
STEEL SHIMS
Use smallest number of shims possible, but no more than four (4). Shims shall be flat and straight, free
from burrs, slag, or dents. If shims are bent, damaged, rusty, or otherwise deformed, they shall not be
used. Shims shall be able to bear the weight of the supported item without deforming or becoming
thinner over time. Always use the thickest shims possible to minimize number of shims used. Before
reusing shim stacks, they should either be cleaned or new shims should be used.
UNIT WEIGHT AND CLEARANCES
A) Note the load tolerance of the floor
Refer to Table 3.1 for list of UPS weights.
UPS Capacity (kVA)
Weight (lb.)
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL

Table 3.1 List of UPS Weights

1200
1250
7270
7270
MITSUBISHI ELECTRIC 9900D SERIES UPS
Page Number:
1500
1600
9750
9750
3-4
2000
11,470

Advertisement