Maersk Container Industry Star Cool SCI-20 Operating And Service Manual page 56

Refrigeration unit
Hide thumbs Also See for Star Cool SCI-20:
Table of Contents

Advertisement

F02 SW version
Function:
Viewing of controller software version and revision.
Value:
-
F03 FC type
Function:
Viewing and setting of actual FC type.
Value:
Set as DANFOSS or NONE for no FC mounted (see "25.1 FC bypass" p. 98). For CIM 5 units, can be
set manually to FC 2.0.
F04 FC SW ver
Function:
Viewing of FC software version.
Value:
-
F05 Phase direction
Function:
Setting of phase direction.
Value:
Is only possible when AL 423 is active. Default setting is AUTO for automatic phase detection -
automatically selected when the unit has been switched off for more than 30 min. before switching
it on again. Can be used for manual phase setting: Setting as CW for clockwise rotation or CCW for
counter-clockwise rotation. If manual phase direction is set, heat is reduced to 60% of max.
F06 Air Ex 0 calibration
Function:
Zero adjust of air exchange sensor when the air inlet is closed.
Value:
Actual value of sensor is set to zero when Enter key
F07 Low press type
Function:
Set the pressure transmitter that is physically mounted for low pressure measurement. Press
Enter for 3 sec. to make the selection.
Value:
AKS, NSK or DST.
F08 High press type
Function:
Set the pressure transmitter that is physically mounted for high pressure measurement. Press
Enter for 3 sec. to make the selection.
Value:
AKS, NSK or DST.
F09 Valve type
Function:
Set the valve type to correspond to physical mounted type.
Value:
R134a only, R134a/R513A.
F10 Model code
Function:
Configure the reefer unit model value.
Value:
Model
SCU-40
SCU-40-W
SCU-40-AV+
Water-cooled condenser
off
on
off
is pressed twice.
CA
AV/AV+
off
off
off
off
off
on
55 of 116 pages