Manual Defrost - Maersk Container Industry Star Cool SCI-20 Operating And Service Manual

Refrigeration unit
Hide thumbs Also See for Star Cool SCI-20:
Table of Contents

Advertisement

48 of 116 pages
O07 O2 setpoint
Function:
O
setpoint.
2
Value:
Range 3 - 21%.
O08 CO2 setpoint
Function:
CO
setpoint.
2
Value:
Range 1 - 19.8%.
O09 Active application
Function:
Actual application.
Value:
- Std (standard)
- AV (automatic ventilation)
- AV+ (automatic ventilation +)
- CA (controlled atmosphere)
O10 Manual defrost
Function:
Go to manual defrost sub menu.
Value:
None.
O13 Flush mode
Function:
Activating command will allow very high levels of CO
Value:
On, off.

11.15 Manual defrost

A manual defrost is only accepted if Tevap less than 15°C (59°F). Defrosting is manually initiated
by pressing the
key or using the O10 Manual defrost menu, selecting specific defrost type and
holding it for 3 sec. The display shows the
G01 Start normal
Function:
Defrost where defrost type is selected automatically.
Value:
Default OFF. Select ON and hold for 3 seconds to start defrosting.
G03 Start air
Function:
Defrost using evaporator fan only.
Value:
Default OFF. Select ON and hold for 3 seconds to start defrosting.
G04 Start hot gas
Function:
Defrost using hot gas only. Requires Tamb to be above +5°C (41°F).
Value:
Default OFF. Select ON and hold for 3 seconds to start defrosting.
G05 Start electrical
Function:
Defrost using electrical heater only.
Value:
*/#
*
*
for 4 hours, then returning to normal control.
2
icon as an acceptance of defrost initiation.