Fc Self Test - Maersk Container Industry Star Cool SCI-20 Operating And Service Manual

Refrigeration unit
Hide thumbs Also See for Star Cool SCI-20:
Table of Contents

Advertisement

51 of 116 pages
Function:
Manual condenser fan on/off. Note that value is only accepted if control is in the manual mode
(menu item M01 is MANUAL).
Value:
Set to OFF, LO (low speed) or HI (high speed).
M05 Compressor freq
Function:
Manual setting of compressor frequency. Note that value is only accepted if control is in the manu-
al mode (menu item M01 is MANUAL).
MANUAL: Compressor frequency is set.
Value:
MANUAL: Set to OFF (compressor stop) or value between 20 and 100 Hz.
M06 Expansion valve
Function:
Manual setting of expansion valve % opening. Note that value is only accepted if control is in the
manual mode (menu item M01 is MANUAL) and compressor is not running.
Value:
Set from 0 to 100%.
M07 Hot gas valve
Function:
Manual setting of hot gas valve % opening. Note that value is only accepted if control is in the
manual mode (menu item M01 is MANUAL).
Value:
Set from 0 to 100%.
M08 Economizer valve
Function:
Manual setting of economizer valve % opening. Note that value is only accepted if control is in
the manual mode (menu item M01 is MANUAL).
Value:
Set from 0 to 100%.
M09 Air Ex auto
Function:
Manual setting of external air valve % opening. Note that value is only accepted if control is in
the manual mode (menu item M01 is MANUAL).
Value:
0-100%.
M10 Vacuum pump
Function:
Manual control of vacuum pump. Note that value is only accepted if control is in the manual mode
(menu item M01 is MANUAL).
Value:
ON/OFF.
M11 FC Selftest
Function:
Leads to the FC self-test sub menu.
Value:
Go to the FC selftest sub menu.
11.18.1 FC self-test
J01 Start Self Test
Function:
Start the frequency converter built-in self-test.
Value:
Start.