Service; Measurement - GE Kelman DGA900 Operator's Manual

Transformer oil dissolved gas and moisture monitor
Table of Contents

Advertisement

6.11 Service

6.11.1 Measurement

Select Service > Measurement to open the Measurement Settings page as shown in
Figure 6-39. The Normalization Temperature is a thermostatically controlled internal target
temperature for the Analysis module. Depending on the region, one of two temperatures
can be set 0 °C or 20 °C.
Figure 6-39: Measurement Settings
The following Measurement Flags are available:
Nitrogen Enabled — displays measurement data for nitrogen. This also activates the
display of Total Dissolved Gases (TDG) (disabled by default).
TDG Enabled — lists the Total Dissolved Gases (TDG). Inactive if nitrogen measurement is
not enabled. TDG = H
TDH Enabled — lists the Total Dissolved Hydrocarbons. (TDH). TDH = CH
C
H
2
6.
Estimated Safe Handling Limit (ESHL) – expresses the concentration of gases contained
within the oil sample as a percentage. This is a safety indicator and is used to assess the
associated risk of the oil sample. ESHL = H
C
H
/LevelC
H
2
6
2
MA-025 – DGA 900 Operator Guide – Rev 2.0
+ CO
+ CO + C
2
2
+ C
H
/LevelC
H
+ C
6
2
4
2
4
2
H
+ C
H
+ CH
+ C
H
2
4
2
6
4
2
/LevelH
+ CH
/LevelCH
2
2
4
H
/LevelC
H
4
2
4.
+ O
+ N
2
2
2.
+ C
H
+ C
4
2
2
2
+ CO/LevelCO +
4
12-Apr-19
Page 41 of 92
H
+
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents