Section 3 • Installation
NOTICE
Vilter compressors are to be installed and connected
to the customer-provided piping. Vilter expects this
piping to be designed and built following ASME B31.3
Process Piping Guide, plus any other local applicable
codes, and that the installation will be performed by
qualifi ed personnel only.
Delivery Inspection
Every equipment supplied by Vilter is thoroughly in-
spected at the factory. However, damage can occur in
shipment. For this reason, the compressor should be
thoroughly inspected upon arrival, prior to off-loading.
Any damage noted should be photographed and report-
ed immediately to the transportation company. This
way, an authorized agent can examine the compres-
sor, determine the extent of damage and take neces-
sary steps to rectify the claim with no serious or costly
delays. At the same time, the local Vilter representa-
tive or the home office should be notified of any claims
Bareshaft Compressor Lifting Points and Weights
Models
Gaterotor
Bearing Housing
97-127
3.3 lbs (1.6 kg)
291-601
19 lbs (9 kg)
751-901
28 lbs (13 kg)
1051-1301
37 lbs (17 kg)
1501-2101
54 lbs (24 kg)
2401-3001
58 lbs (27 kg)
Table 3-2. Bareshaft Compressor Component Lifting Hole Sizes
Models
Discharge
Manifold (Side)
97-127
A & B Lifting Points: 1/2 - 13 UNC -2B
291-601
5/8-11 UNC -2B
751-901
5/8-11 UNC -2B
1051-1301
5/8-11 UNC-2B
1501-2101
5/8-11 UNC -2B
2401-3001
5/8-11 UNC -2B
VSS/VSR/VSM/VSH/VSSH Compressor • Installation, Operation and Service Manual • Emerson • 35391S
Table 3-1. Bareshaft Compressor Component Weights
Gaterotor Bearing
Housing Cover
8 lbs (4 kg)
11 lbs (5 kg)
11 lbs (5 kg)
13 lbs (6 kg)
19 lbs (9 kg)
32 lbs (15 kg)
A
B
Discharge
Manifold (Top)
5/8-11 UNC -2B
5/8-11 UNC -2B
5/8-11 UNC -2B
5/8-11 UNC -2B
5/8-11 UNC -2B
made within ten (10) days after its discovery. Refer to
Compressor Inspections Prior to Installation for addi-
tional recommendations.
Rigging and Lifting of the Compressor
When rigging and lifting a compressor unit, use proper
lifting device capable of lifting and maneuvering the
weight and size of the compressor unit. Use only
qualifi ed personnel and additional personnel and
lifting equipment (i.e. spreader bar) as required.
Failure to comply may result in death, serious injury
and/or damage to equipment.
Only qualified personnel shall operate rigging and lifting
equipment. Ensure that the lifting device is capable of
lifting the weight of the compressor, refer to the sup-
plied Vilter General Assembly (GA) drawing, and to Table
3-1 for weights of bare shaft compressors.
Component Weights
Discharge
Manifold
N/A
125 lbs (57 kg)
177 lbs (80 kg)
274 lbs (125 kg)
349 lbs (158 kg)
788 lbs (358 kg)
Component Lifting Hole Sizes
C
Main Compressor
Assembly ONLY
(Discharge)
-
5/8-11 UNC -2B
5/8-11 UNC -2B
3/4-10 UNC -2B
5/8-11 UNC -2B
5/8-11 UNC -2B
WARNING
Main Compressor
Assembly ONLY
249 lbs (113 kg)
1105 lbs (502 kg)
1450 lbs (658 kg)
2006 lbs (910 kg)
3151 lbs (1429 kg)
4152 lbs (1883 kg)
D
Main Compressor
Assembly ONLY
(Suction)
-
5/8-11 UNC -2B
3/8-16 UNC-2B
5/8-11 UNC -2B
5/8-11 UNC -2B
3/8-16 UNC -2B
5/8-11 UNC -2B
3/8-16 UNC -2B
3/4-10 UNC -2B
5/8-11 UNC -2B
Gaterotor
Cover
10 lbs (5 kg)
46 lbs (21 kg)
33 lbs (15 kg)
42 lbs (19 kg)
70 lbs (32 kg)
150 lbs (68 kg)
E
Gaterotor
Cover
-
-
3 – 1