Troubleshooting; The Manual Tool; Service Parameters - Emerson VILTER VSS Installation, Operation And Service Manual

Single screw bare shaft compressor
Hide thumbs Also See for VILTER VSS:
Table of Contents

Advertisement

ICM/ICAD Motorized Valve

Troubleshooting

The Manual Tool

Service Parameters

10
Installation, Programming, and Troubleshooting
The manual tool should always be ordered with any ICM/ICAD assembly. This tool gives the
user the ability to remove the ICAD actuator and manually rotate the valve in the open or
close direction depending on need and application. When using the manual tool, a clock-
wise rotation will open the valve and a counter-clockwise rotation will close the valve.
NOTE:
It is very important to remember that when rotating the valve manually you are changing
the position from that in the actuator's memory. If power is removed from the actuator prior
to using the manual tool, no problem will occur because, once the ICAD is powered up again,
it will automatically recalibrate to the fully closed position before returning to the position in
memory to which the control signal last set the valve. This recalibration will not occur if
power is not removed from the ICAD prior to using the manual tool, and erroneous operation
will likely occur. Always remove power before using the manual tool, and restore power
afterward to ensure recalibration and trouble-free operation.
The user will be able to troubleshoot and determine many of the conditions and set points
within the ICAD by accessing the Service Menu. A list of those service parameters follows
below:
Service Menu
Display
Description
name
¡50
OD %
¡51
AI [mA]
¡52
AI [V]
¡53
AO [mA]
DI
¡54
DO Close
¡55
DO Open
¡56
DO Alarm
¡57
MAS mP SW
¡58
ver.
SLA mP SW ver.
¡59
It is also possible to restore the original factory settings to the ICAD by the following
procedure:
To restore factory settings:
1. Remove the power supply.
. Activate down arrow and up arrow push buttons at the same time.
3. While holding the up and down arrow reconnect the power supply.
4. Release down arrow and up arrow push buttons.
5. When the display on ICAD is alternating between showing: CA and A1 the factory
resetting is complete.
DKRCI.EI.HT0.A1. / 50H1639
Min. Max. Unit Comments
0
100
%
ICM valve Opening Degree
0
0
mA Analog Input signal
0
10
V
Analog Input signal
0
0
mA Analog Output signal
0
1
-
Digital Input signal
0
1
-
Digital Output Closed status. ON when OD < 3 %
0
1
-
Digital Output Open status. ON when OD > 97 %
0
1
-
Digital Output alarm status. ON when an alarm is detected
0
100
-
Software version for MASTER Microprocessor
0
100
-
Software version for SLAVE Microprocessor
 Danfoss (USCO / MKS), 11- 006

Advertisement