2.6. Technical data

II 2G Ex ib IIB T4 Gb
0158
General data
Device group
Device category
Ignition protection type
Explosion group
Temperature class
Device protection level
Min. / max. storage/transport temperature
Min. / max. ambient temperature
Min. / max. media temperature
Condensate inlet
Condensate discharge
Condensate
Weight
Materials
Performance data
Max. compressor capacity
Max. refrigeration dryer performance
Max. drainage rate (short-term)
Ø drainage rate
Min./max. operating pressure
Electrical data
Operating voltage
(connection to intrinsically safe power supply as specified below)
Power consumption
Recommend wire cross-section
Protection class
Recommended power supply
Alarm output
Solenoid valve
BEKOMAT
3/6 CO Ex, 3/6 E Ex
®
IP 65
3 CO Ex
3 E Ex
+1 ... +60 °C
+1 ... +60 °C
+1 ... +60 °C
3 x G¾-inside
 (optional: NPT fitting)
1 x G½-inside (optional: NPT fitting)
oil-contaminated 
oil-contaminated 
condensate |
condensate
oil-free, possibly 
| oil-free 
aggressive
condensate
condensate
3.4 kg (empty) 8.0 kg (empty) 6.7 kg (empty) 14.0 kg (empty)
Housing: 
Housing: 
aluminium,
Stainless steel
hard-coated
3 CO Ex
3 E Ex
100 m³/min
e.g. Central/Southern Europe,
Central America
200 m³/min
e.g. Central/Southern Europe,
Central America
540 l/h
43 l/h
0.8 ... 16 ... 1.2 bar 16 bar (see type plate)
3 CO Ex
3 E Ex
U
= 12.0 V / U
rated
I
= 150 mA / P
max
P ≤ 1.9 W
3 x 0,75 ... 1.5 mm² (AWG 16 ... 20)
Power supply unit
85 - 230 VAC
4005140
Optocoupler output for signalling to a NAMUR interface accord-
ing to DIN EN 60947-5-6
Recommended switch amplifier
230 VAC for BEKOMAT
EN 60079-0:2012 + A11
EN 60079-11:2012
ll2G Ex ia llC T6 or Ex ia ll T5
PTB 01 ATEX 2101
Installation and operating manual
6 CO Ex
6 E Ex
ll
2G
ib
llB
T4
Gb
2 x G¾-inside
(optional: NPT fitting)
1 x G1-inside
(optional: NPT fitting)
oil-contaminated 
oil-contaminated 
condensate |
condensate
oil-free, possibly 
| oil-free 
aggressive
condensate
condensate
Housing: 
Housing: 
aluminium,
Stainless steel
hard-coated
6 CO Ex
6 E Ex
1000 m³/min
e.g. Central/Southern Europe,
Central America
2000 m³/min
e.g. Central/Southern Europe,
Central America
1700 l/h
274 l/h
6 CO Ex
6 E Ex
= 12.6 V
max
= 1.9 W
max
IP 65