Advertisement

Problem
Monitor readings are inaccu-
rate.
Device is unable to register
to the Pulse Pro network or
the device does not rejoin
the network after system
reboot.
3A5411J
Cause
Tank geometry incorrectly
defined.
Tank Level Monitor has not
been updated with latest
adjustments made within The
profile ID on the Pulse sys-
tem.
Fluid surface is moving while
reading is being taken.
Pipe adapters installed in the
tank bung.
Tank Level Monitor is not per-
pendicular to top of fluid.
Inside tank obstruction.
Device is not meshing prop-
erly with the device network.
Troubleshooting
Solution
See Tank Level Monitor Soft-
ware Guide or PC Software
Guide for details.
Manually push DISPLAY but-
ton on TLM.
Ensure pump is not operating
and that nothing is disturbing
the surface of the fluid during
readings.
Ensure there are no adapters
installed in the tank bung.
Level tank so that it is per-
pendicular to top of the fluid
and/or realign Tank Level
Monitor.
Install in different tank bung
to avoid tank obstruction.
Toggle to Discovery mode on
the HUB. Wait one minute
and toggle it back. Press the
button to attempt a network
connection. If this does not
resolve the issue, remove the
batteries, wait two minutes
then reinstall the batteries.
13