Chapter 1
Installation

Connect the Wiring

Table 3 - 1442 Series Color Band Table
Cable Length
0.5 m
1.0 m
5.0 m
9.0 m
32
This section describes the wiring connections for the 1442 Series Eddy Current
Probe system.
The 1442 Series includes color–coded bands on the ends of each component.
The color–coded bands help you identify the length of the extension cable and
the length of the probe so that the total system length (5 or 9 meters) can be
matched to the appropriate driver. When the system is properly "sized, " the color
bands for the probe, extension cable, and driver will match.
Sensor
Color Band
Length
Yellow
4.0 m
Black
4.5
Blue
8.0
Red
8.5
TIP
TIP
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014
Extension Cable
Probe End Color
Driver End Color
Band
Band
Black
Blue
Yellow
Blue
Black
Red
Yellow
Red
WARNING: Make sure the wiring and connections are performed by a
person with knowledge in instrumentation.
WARNING: Make sure you ground your system. Never apply power until
all wiring and connection work has been completed. If this is not
followed there is a possibility of electrocution.
ATTENTION: Make sure to tighten the collar of the connector by hand.
Using a tool to tighten the collar can damage the connector. If the
installation environment does not allow proper tightening by hand and
there is a possibility that it can come loose, tighten an additional 1/4
turn using pliers after tightening by hand:
• Do not apply excessive force on the screws of the connector. The
connector can be damaged
• Do not cut the sensor or extension cables shorter. It can cause problems,
such as not being able to perform up to specifications.
Make sure that the cable is not twisted when connecting the connectors.
Twisting stress on the cable can slowly loosen the connection.
If a twisting force is applied to the direction where the collar is loosened,
twist the extension cable slightly to the opposite direction of the collar
tightening direction before connecting. Then connect the connector and
tighten the collar.
We recommend that excessive extension cables be stored in the cable
storage box. If it is unavoidable to store inside the driver housing, do not
force excessive cables into the housing.
Driver
System Cable
Color
Length
Band
5.0
Blue
9.0
Red