Once all the cables have been reconnected slide the front surround assembly onto the chassis plates and fit the 4 self
tap screws that hold the unit together.
Slide the case back onto the recorder ensuring it is fitted the right way round. The cooling slots should be at the top of
the unit.
Finally fit the four M3 screws that hold the case to the chassis.

Touch Screen Calibration

Calibration of the touch screen may not be required.
Test the touch screen calibration by using the "Touch Test" option on the recorder. This allows you to touch the screen
and check a cursor moves to the correct position. This can be accessed by entering the "Main Menu", then "Screen",
then "Touch Test".
If the touch screen needs recalibrating:
Exit the touch test screen with the "finish" button the press "Calibrate". This will take you to the calibration screen.
Using the stylus touch the screen at the centre of the cursor. Hold the stylus there until the cursor moves. Continue
touching and holding on the cursor until calibration is complete.
Once calibration is complete, touch the screen once more to exit calibration.
The new calibration can be tested again with "Touch test" if required.
More information on touch screen calibration can be found in the product user manual.