Communication Parameter Configuration; Communication Related Parameters Setting In Fe; Parameter Configuration Of Master; Gsd File - Bosch Rexroth Fe PROFIBUS-DP Bus Adapter Instruction Manual

For frequency converter
Table of Contents

Advertisement

PROFIBUS-DP Bus Adapter

7 Communication Parameter Configuration

7.1 Communication related parameters setting in Fe

Function code
Setting of operation com-
b00
mand source
Setting of frequency com-
b02
mand source
Selection of communication
H08
protocol
H09
Address of local machine
Action selection in case of
H12
communication disconnec-
tion
Detection time for communi-
H13
cation disconnection
H14 – H21
Process data
Tab. 7-1: PROFIBUS-DP communication related function codes of frequency converter Fe
If parameter [b00]=5, when the frequency converter is stopped by
the Stop key on the operating panel, adapter is isolated from com-
munication software of the frequency converter. If communication is
to be re-established, Stop and Reset commands must be sent to the
frequency converter by the adapter.

7.2 Parameter configuration of master

Parameter configuration for related master may refer to instructions for the
master. The address configured for slave in the master should be consistent
with the parameter address configured for the slave. Communication baud rate
and PPO type is determined by the master.

7.3 GSD file

Users may log on the website of the company at
download electronic database document (RXFEDP01.gsd) and bit map docu-
ment (RX_FE*.bmp) pack for fieldbus adapter. For specific operation and
PROFIBUS system configuration method, please refer to related system configu-
ration documents.
DOK-RCON01-PROFIBUS***-IB04-EN-P
Parameter name
Communication Parameter Configuration
Parameter value setting range
5: Master controls Run/Stop, Stop key on operating
panel is valid
6: Master controls Run/Stop, Stop key on operating
panel is invalid
12: Master sets a frequency
1: PROFIBUS
1 – 126
0: stop; 1: continue to run
0.0: invalid 0.1 – 60.0s
0 – 7, refer to
tab. 6-11 "Status monitoring value
and parameter setting corresponding to process da-
ta PZD3 – PZD10" on page 27
tions for details.
www.boschrexroth.com/fe
Bosch Rexroth AG
and related descrip-
to
29/35