ABB DSQC1000 Applications Manual page 32

Profinet anybus device
Table of Contents

Advertisement

4 Configuring the anybus device
4.4.1 Configuring an external controller using Siemens Step7 PC tool
Continued
15
16
17
18
Continues on next page
32
Action
Expand the DI/DO folder for the DSQC
688 device in the tree structure.
Select the DSQC 688 icon added to the
fieldbus network.
Drag the correct input size to slot 1and
the correct output size to slot 2.
The input size shall be the same as the
output size configured in the IRC5 control-
ler. The output size shall be the same as
the input size configured in the IRC5
controller.
Note
Inputs and outputs must be added to the
correct slots, otherwise the communica-
tion with the device will not work properly.
If another size, then 64 byte input and 64
byte output are used, the size must be
changed in the UNIT TYPE in the IRC5
controller configuration.
Right-click on the DSQC 688 icon and
select Object Properties.
© Copyright 2008-2016 ABB. All rights reserved.
Note
xx0800000195
xx0800000196
Application manual - PROFINET Anybus Device
3HAC050968-001 Revision: C