Technical Specifications
About this task:
Table 2: Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD
Supply Voltage
Current Consumption
Terminations
Network Sensor
Addressing
Wire Size
Communication Rate
Temperature Measurement Range
Humidity Measurement
Range
Temperature Sensor Type
Humidity Sensor Type
Temperature Resolution
Temperature Accuracy
Humidity Element
Accuracy
Time Constant
Default Temperature Setpoint Adjustment
Range
Ambient Conditions
Compliance
Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD Installation Guide
9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
Temperature Only
21 mA Maximum (Non-transmitting)
Models
Temperature and
25 mA Maximum (Non-transmitting)
Humidity Models
Modular Jack or Screw Terminal Block
NS-BHx7x03-x, NS-
DIP Switch Set from 200 to 203; Factory Set at 203
BPB7003-x, NS-
BTx7003-x, Models
All Other Models
Fixed Address of 199
Modular Jack
24 or 26 AWG (0.5 or 0.4 mm Diameter); Three Twisted Pair (Six
Models
Conductors)
Screw Terminal
18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter)
Block Models
Recommended
Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
32.0°F/0.0°C to 104.0°F/40.0°C
Full Range
0 to 100% RH
Calibrated Range
10 to 90% RH
Local 1k Ohm Platinum Resistance Temperature Detector (RTD);
Class A per IEC 60751
Thin Film Capacitive Sensor
±0.5F°/±0.5C°
NS Series Network
±1.0F°/±0.6C°
Zone Sensor
Temperature
0.35F° at 70°F (0.19C° at 21°C)
Element Only
NS-BPB700x-x
±2% RH for 20 to 80% RH at 50°F to 95°F (10°C to 35°C);±4% RH for 10
Models
to 20% and 80 to 90% RH at 50°F to 95°F (10°C to 35°C)
NS-BHx7x0x-x
±3% RH for 20 to 80% RH at 77°F (25°C)±6% RH for 10 to 20% and 80
Models
to 90% RH at 77°F (25°C)
10 Minutes Nominal at 10 fpm Airflow
50.0°F/10.0°C to 86.0°F/30.0°C in 0.5° Increments
Operating
32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing;85°F (29°C)
Maximum Dew Point
Storage
-4 to 140°F (-20 to 60°C); 5 to 95% RH, Noncondensing
BACnet
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart
International
Sensor (B-SS)
United States
UL Listed, File E107041, CCN PAZX,Under UL 916, Energy
Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada
UL Listed, File E107041, CCN PAZX7,Under CAN/CSA C22.2 No. 205,
Signal Equipment
Industry Canada, ICES-003
Note: Excludes the NS-BTV700x-0 models.