Repair Information

If the NS Series Network Sensor fails to operate within its specifications, replace the unit. For a replacement network
sensor, contact the nearest Johnson Controls representative.

Technical Specifications

Table 2: Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors without LCD
Supply Voltage
Current
Temperature
Consumption
Only Models
Temperature and
Humidity Models
Terminations
Network
NS-
Sensor
BTN7003-0, NS-
Addressing
BTP7003-0,NS-
BTL7003-0, NS-
BHN7003-0,NS-
BHP7003-0
Models
All Other Models Fixed Address of 199
Wire Size
Modular Jack
Models
Screw Terminal
Block Models
Communication Rate
Temperature Measurement
Range
Humidity
Full Range
Measurement
Calibrated Range 10 to 90% RH
Range
Temperature Sensor Type
Humidity Sensor Type
Temperature
NS Series
Accuracy
Network Zone
Sensor
Temperature
Element Only
Humidity Element Accuracy
Time Constant
Default Temperature Setpoint
Adjustment Range
Ambient
Operating
Conditions
Storage
4
Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors without LCD Installation Guide
9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
13 mA Maximum (Non-transmitting)
17 mA Maximum (Non-transmitting)
Modular Jack or Screw Terminal Block
DIP Switch Set from 200 to 203; Factory Set at 203
24 or 26 AWG (0.5 or 0.4 mm Diameter); Three Twisted Pair (Six Conductors)
18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter) Recommended
Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
32.0°F/0.0°C to 104.0°F/40.0°C
0 to 100% RH
Local 1k Ohm Platinum Resistance Temperature Detector (RTD); Class A per IEC
60751
Thin Film Capacitive Sensor
±1.0F°/±0.6C°
0.35F° at 70°F (0.19C° at 21°C)
±3% RH for 20 to 80% RH;±6% RH for 10 to 20% and 80 to 90% RH
10 Minutes Nominal at 10 fpm Airflow
±5.0F°/±3.0C°
32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing;85°F (29°C) Maximum Dew
Point
-40 to 158°F (-40 to 70°C); 5 to 95% RH, Noncondensing