Repair Information; Technical Specifications - Johnson Controls NS Series Installation Manual

Vertical wallbox-mounted or surface-mounted occupancy sensing network sensors without lcd

Advertisement

This addressable model is shipped with both switches
set to ON, resulting in a device address of 203. Device
addresses can be DIP switch set from 200 to 203; see
Figure 3 and Table 1 for more details.
If the occupancy sensing NS Series Network Sensor fails to operate within its specifications, replace the unit. For a
replacement network sensor, contact the nearest Johnson Controls representative.

Technical Specifications

Table 2: Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sensors without
LCD
Supply Voltage
Current
Temperature
Consumption
Only Models,
and Motion
Detection Only
Models
Temperature
and Humidity
Models
Terminations
Network
NS-MNN7003-0
Sensor
Model
Addressing
All Other
Models
Wire Size
Modular Jack
Models
Screw Terminal
Block Models
Communication Rate
Temperature Measurement
Range (Temperature Only
Models, and Temperature and
Humidity Models)
4
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sensors without LCD Installation
Guide
9.8 to 16.5 VDC; 15 VDC nominal (from SA Bus)
13 mA maximum (non-transmitting)
17 mA maximum (non-transmitting)
Modular jack or screw terminal block
DIP switch set from 200 to 203; factory set at 203
Fixed address of 199
24 or 26 AWG (0.5 or 0.4 mm diameter); three twisted pair (six conductors)
18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended
Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
32.0°F/0.0°C to 104.0°F/40.0°C
Figure 3: Dual-Switch DIP Switch Block (NS-MNN7003-0
Model)
Table 1: Network Sensor Addressing (NS-MNN7003-0
Model)
DIP Switch
Switch 2
Address
200
OFF
201
OFF
202
ON
203
ON

Repair Information

Switch 1
OFF
ON
OFF
ON