Acromag BusWorks XT Series User Manual

Interposing relay board six channel digital inputs six mechanical relay outputs, normally open
Hide thumbs Also See for BusWorks XT Series:

Advertisement

Quick Links

sales@artisantg.com
artisantg.com
(217) 352-9330 |
|
Click HERE
Find the Acromag BusWorks XTA-MRNO at our website:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BusWorks XT Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Acromag BusWorks XT Series

  • Page 1 (217) 352-9330 | Click HERE Find the Acromag BusWorks XTA-MRNO at our website:...
  • Page 2 Six Mechanical Relay Outputs, Normally Open USER’S MANUAL ACROMAG INCORPORATED Tel: (248) 295‐0880 30765 South Wixom Road Fax: (248) 624‐9234 Wixom, MI 48393‐2417 U.S.A. email: sales@acromag.com Copyright 2014, Acromag, Inc., Printed in the USA. 8500‐960G Data and specifications are subject to change without notice.
  • Page 3: Table Of Contents

    Acromag, that this is your responsibility. The information of this manual may change without notice. Acromag makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Further, Acromag assumes no responsibility for any errors that may appear in this manual and makes no commitment to update, or keep current, the information contained in this manual.
  • Page 4: Description

    Symbols on equipment: The XTA‐MRNO‐6 is a six channel digital input board with six, normally open, isolated mechanical relay outputs for use with BusWorks XT Series DIO modules, or other digital output modules, for the purpose of driving high energy loads. This module serves as an interim digital interface for driving high voltage (up to 250VAC, Means “Refer to User’s Manual...
  • Page 5: Mechanical Dimensions

    DIN rail clip and use it as a lever to force the DIN rail spring clip down while pulling the bottom of the module outward until it disengages from the rail. Tilt the module upward to lift it from the rail. Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...
  • Page 6: Electrical Connections

    (use 0.5‐0.6nM torque). Since common mode voltages can exist on I/O wiring, adequate wire insulation should be used and proper wiring practices followed. As a rule, I/O wires are normally separated from power and network wiring for safety, as well as for low noise pickup. Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...
  • Page 7: Power Connections

    DIN rail bus when coupled to the DIN rail bus connector (Acromag Model 1005‐070) and a bus terminal block (Acromag 1005‐220 or 1005‐ 221). This optional method can allow several modules to share a single power supply without wiring to each individually.
  • Page 8 Important – End Stops: If this module uses the optionally powered (or redundantly powered) via the DIN rail bus for hazardous location installations (Class I, Division 2 or ATEX Zone 2) it must use two end stops (Acromag 1027‐222) to secure the terminal block and module (not shown).
  • Page 9: Digital Input Connections

    Avoid inadvertent (extra) connections to earth ground at points other than those indicated, as this could drive ground loops and negatively affect operation. Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...
  • Page 10: Relay Output Connections

    LOCATE RELAY NEAR LOAD (DIODE RECTIFIER) RETURN DC-POWERED RELAY LOCATE THE SHUNT DIODE LOCAL TO THE DC INDUCTIVE LOAD. NOTE THE CATHODE OF THE DIODE POINTS TO THE POSITIVE SIDE OF THE INDUCTIVE LOAD. EARTH GROUND RETURN Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...
  • Page 11: Block Diagram

    The bus power and power terminal connections are diode coupled energized state. to the same point in the circuit, allowing redundant/shared power connection. Transient voltage suppressors and bypass capacitors help protect input and power terminals from potentially damaging transient energy. Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...
  • Page 12: Troubleshooting

    Please refer to Acromag’s Service Policy and Warranty Bulletins on our web site, or contact Acromag for complete details on how to obtain repair or replacement.
  • Page 13: Accessories

    (0.1uF) is included at every input. TVS diodes are rated for a filtering. working voltage up to 38VDC, a breakdown voltage of 72VDC, and a clamping voltage of 100VDC. Input Current: 3.2 mA at 32VDC, typical. Inputs include 10KΩ pull‐downs to return. Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...
  • Page 14: Relay Outputs

    I/O Connectors: Removable plug‐in type terminal blocks rated for 12A/250V; AWG #26‐12, stranded or solid copper wire. Case Material: Self‐extinguishing polyamide, UL94 V‐0 rated, color light gray. General purpose NEMA Type 1 enclosure. Circuit Board: Military grade fire‐retardant epoxy glass per IPC‐4101/98. Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...
  • Page 15: Environmental

    II 3 G Ex nA nC IIC T4 Gc ‐40 C ≤ Ta ≤ +80 DEMKO 15 ATEX 1561X X = Special Conditions The equipment shall only be used in an area of not more than pollution degree 2, as defined in EN 60664‐1. Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...
  • Page 16: Reliability Prediction

    • Page 14 Reliability Prediction (MTBF / FIT was TBD) 21‐FEB‐2014 CAP/ARP Added cULus Mark to this model (removed pending). 21‐JUL‐2014 CAP/ARP Added UL caution symbols / statements. Added ATEX symbols / statements. 15‐OCT‐2015 CAP/ARP 22‐AUG‐2016 CAP/MJO Corrected “Circuit Board” specification. Acromag, Inc. Tel: 248‐295‐0880 http://www.acromag.com...