16. Commissioning
The fans used for the CRL-6200 have a k value of 188.
1200
V = 188 x √Dp
1000
800
600
400
200
0
3000
3500
Δp
[Pa] 290
347
[m³/h] 3200 3500 3800 4100 4400 4700 5000 5300 5600 5900 6200
V
The fans used for the CRL-9000 have a k value of 240.
1400
V = 240 x √Dp
1200
1000
800
600
400
200
0
3800
4600
Δp
[Pa] 278
352
[m³/h] 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000
V
Further settings for the BMK programming unit can be found in the operating
instructions for the WRS-K control unit.
Accessories are installed in accordance with separate instruction manuals
which are provided with the relevant accessories.