Wolf CRL-iD-1300 Installation And Maintenance Instructions Manual page 34

Comfort ventilation unit with thermal wheel heat exchanger
Table of Contents

Advertisement

CRL-3500 effective pressure
Δp = effective pressure
(symbolic representation)
CRL-4800 effective pressure
Δp = effective pressure
(symbolic representation)
34
16. Commissioning
The fans used for the CRL-3500 ave a k value of 121.
1000
V = 121 x √Dp
800
600
400
200
0
1500
Δp
[Pa]
197
247
[m³/h] 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500
V
The fans used for the CRL-4800 have a k value of 148.
1200
V = 148 x √Dp
1000
800
600
400
200
0
1900
2400
Δp
[Pa]
201
263
[m³/h] 2100 2400 2700 3000 3800 3600 3900 4200 4500 4800
V
w
2000
2500
Flow rate [m³/h]
301
361
427
498
w
2900
3400
Flow rate [m³/h]
333
411
497
592
3000
3500
574
656
744
837
3900
4400
4900
694
805
924
1052
3064361_201710