Flow rate calculation
CRL-1300 effective pressure
Δp = effective pressure
(symbolic representation)
CRL-2500 effective pressure
Δp = effective pressure
(symbolic representation)
3064361_201710
16. Commissioning
The flow rate is calculated using the effective pressure method. This involves
comparing the static pressure upstream of the inlet nozzle with the static
pressure in the inlet nozzle.
The flow rate can be calculated from the effective pressure Δp
(differential pressure of the two static pressures) using the following equation.
The doors must be closed to determine the correct flow rate. Route the test
hoses through the unit floor to the outside when conducting the test.
The fans used for the CRL-1300 ave a k value of 76.
1000
V = 76 x √Dp
800
600
400
200
0
1500
Δp
[Pa]
43
62
[m³/h]
500
600
V
The fans used for the CRL-2500 ave a k value of 77.
1200
V = 77 x √Dp
1000
800
600
400
200
0
700
1000
Δp
[Pa]
137
204
[m³/h]
900
1100
V
w
2000
2500
Flow rate [m³/h]
85
111
140
173
700
800
900
1000
w
1300
1600
1900
Flow rate [m³/h]
285
379
487
609
1300 1500 1700 1900 2100 2300 2500
w
3000
3500
209
249
293
1100
1200 1300
2200
2500
2800
744
892
1054