NTS & NTU Series Installation manual True Sine Wave Inverter High Reliable Inverter...
Page 2
NTS/NTU series are MEAN WELL's new generation high-reliability off- g r i d D C - A C p u r e s i n e w a v e i n v e r t e r s . T h e w h o l e f a m i l y h a s N T S - 2 5 0 P / 4 0 0 P, N T S - 3 0 0 / 4 5 0 / 7 5 0 / 1 2 0 0 / 1 7 0 0 / 2 2 0 0 / 3 2 0 0 , and NTU-1200/1700/2200/3200 series .
1 Safety Guidelines 2 Introduction 2.1 Model number Risk of electrical shock and energy hazard. All failures should be examined by the qualified technician. Please do not remove the case of the inverter NTS - 12 US by yourself. Please do not install the inverter in places with high moisture or near AC Socket water.
Page 5
2.3 Specification NTS-250P series NTS-400P series NTS-250P-112 NTS-250P-124 NTS-250P-148 NTS-250P-212 NTS-250P-224 NTS-250P-248 NTS-400P-112 NTS-400P-124 NTS-400P-148 NTS-400P-212 NTS-400P-224 NTS-400P-248 MODEL MODEL RATED POWER(Continuous) RATED POWER(Continuous) 250W 400W OVER RATED POWER(3 Min.) OVER RATED POWER(3 Min.) 287.5W 460W PEAK POWER(10 Sec.) PEAK POWER(10 Sec.) 375W 600W SURGE POWER(30 Cycles)
Page 6
NTS-300 series NTS-450 series NTS-300-112 NTS-300-124 NTS-300-148 NTS-300-212 NTS-300-224 NTS-300-248 NTS-450-112 NTS-450-124 NTS-450-148 NTS-450-212 NTS-450-224 NTS-450-248 MODEL MODEL = US, GFCI, UN = EU, CN, AU, UK, UN = US, GFCI, UN = EU, CN, AU, UK, UN RATED POWER(Continuous) RATED POWER(Continuous) 300W 450W...
Page 7
NTS-750 series NTS-1200 series NTS-750-112 NTS-750-124 NTS-750-148 NTS-750-212 NTS-750-224 NTS-750-248 NTS-1200-112 NTS-1200-124 NTS-1200-148 NTS-1200-212 NTS-1200-224 NTS-1200-248 MODEL MODEL = US, GFCI, UN = EU, CN, AU, UK, UN = US, GFCI, UN = EU, CN, AU, UK, UN RATED POWER(Continuous) RATED POWER(Continuous) 750W 1200W...
Page 8
NTS-1700 series NTS-2200 series NTS-1700-112 NTS-1700-124 NTS-1700-148 NTS-1700-212 NTS-1700-224 NTS-1700-248 NTS-2200-112 NTS-2200-124 NTS-2200-148 NTS-2200-212 NTS-2200-224 NTS-2200-248 MODEL MODEL = US, GFCI, UN = EU, CN, AU, UK, UN = US, GFCI, UN = EU, CN, AU, UK, UN RATED POWER(Continuous) RATED POWER(Continuous) 1500W 1700W...
Page 9
NTS-3200 series NTU-1200 series Built-in UPS function NTS-3200-112 NTS-3200-124 NTS-3200-148 NTS-3200-212 NTS-3200-224 NTS-3200-248 NTU-1200-112 NTU-1200-124 NTU-1200-148 NTU-1200-212 NTU-1200-224 NTU-1200-248 MODEL MODEL = US, GFCI, UN = EU, CN, AU, UK, UN = US, GFCI, UN = EU, CN, AU, UK, UN RATED POWER(Continuous) RATED POWER(Continuous) 3200W...
Page 10
NTU-1700 series Built-in UPS function NTU-2200 series Built-in UPS function NTU-1700-112 NTU-1700-124 NTU-1700-148 NTU-1700-212 NTU-1700-224 NTU-1700-248 NTU-2200-112 NTU-2200-124 NTU-2200-148 NTU-2200-212 NTU-2200-224 NTU-2200-248 MODEL MODEL = US, GFCI, UN = EU, CN, AU, UK, UN = US, GFCI, UN = EU, CN, AU, UK, UN RATED POWER(Continuous) RATED POWER(Continuous) 1500W...
2.5 Derating curve 2.6 Mechanical specification NTS-250P/400P NTS-300,NTS-450,NTS-750,NTU-1200,NTS-1200,NTU-1700 NTS-1700 NTS-250P/400P,NTS-2200/3200,NTU-2200/3200 Screw size of M5 shall be used.( 5 5) φ . M3( 3 5) φ . Natural convection Force air with 25CFM fan for NTS-250P/400P 20 30 35 40 50 60 65 70 (HORIZONTAL) AMBIENT TEMPERATURE ( ) ℃...
Page 13
NTS-300/450 750 NTS/NTU-1200/1700 DC INPUT Chassis Bonding Reverse Polarity Will Damage The Unit. NTS-300 Chassis Bonding Reverse Polarity Will Damage The Unit. NTS-450 Reverse Polarity Will Damage The Unit. DC INPUT Air flow Chassis Bonding direction Air flow direction NTS-750 Reverse Polarity Will Damage The Unit.
Page 14
NTS/NTU-2200/3200 Accessories Optional Quantity MW s Order No. ’ Item Pull Handle Foot pad NTS-Handle Screw M4*2 Pull Handle Air flow Air flow direction direction Foot pad Reverse Polarity Will Damage The Unit. DC INPUT Model NTS/NTU-2200 NTS/NTU-3200 Unit mm...
3.3 Installation procedures 3 Installation & Wiring Please turn off the inverter first. 3.1 Precautions Select proper cable for connection between battery and inverter by The unit should be mounted on a flat surface or holding rack with referring to section 3.4 suitable strength.
3.5 Battery selection 4 User Interface Battery types Lead acid or lithium ion batteries : 4.1 AC panel Voltage range 10 16 5Vdc (12V), 20~33Vdc (24V), 40~66Vdc (48V) : AC output socket : Please refer to Pg. 16 for varies socket for different Battery capacity Please refer to the following table.
Page 17
4.2 DC input panel NTS-1200 NTU-1200 POWER ON/OFF switch: The inverter will turn ON if the switch is in the ON position, and vice versa. Input terminals (+), (-) Frame ground (FG) Ventilation slits: The inverter requires suitable ventilation to work AC OUTPUT AC OUTPUT properly.
4.3 LED Indicator AC Input Indicator: Represents the magnitude of AC main. Status indicator : Green light: The LED is used to indicate the status of inverter, including inverter OK, remote on/off and power saving mode. When AC mains is connected and the voltage is present normally. Flash in green light:...
5 Explanation of Operation 5.2 Function Difference 5.1 Procedure of setting Operating Mode, Output Voltage, NTS-250P/400P NTS-750/1200/1700/2200/3200 NTU-1200/1700/2200/3200 Funtion model NTS-300/450 Support IRC Frequency, and Saving Mode Support RS-232 5.1.1 Output Voltage and Frequency Setting UPS Function Factory settings are either 110Vac/60Hz or 230Vac/50Hz, users are able to adjust the voltage and frequency, through the DIP switch of position 1,2,3 Standard on the AC panel.
O/P load O/P load Parity None PPP,3 Percent Percent 0~100% ASCII Flow Control None (Analog) (Analog) Definition of MEAN WELL RS-232 protocol INVERTER INVERTER 1: INVERTER Mode b0,1 ASCII Mode Mode Command Code Type Command name Bypass Bypass Status Inquiry...
Page 21
49 byte data flow (VVV QQQ SS.S BBB TT.T MMM RR.R DDD PPP Data Funtion Description R/W Range Data type Uint byte name of commandd Q b0b1b2b3b4b5b6b7b8b9b10b11b12b13b14b15b16b17b18) b16,1 INV Fault INV Fault 1: INV Fault ASCII Data Funtion Description R/W Range Data type Uint...
Page 22
Definition of command C ( ) Data Funtion Description R/W Range Data type Uint byte name Data Funtion Description R/W Range Data type Uint byte name 12: 9.0~15.0Vdc Floating Floating 24: 18.0~30.0Vdc Shut Shut ASCII b0,1 1: Remote Shutdown ASCII Volt.
Page 23
(default 110Vac) as an example, when the voltage of AC mains is for NTU series only greater then 127.6Vac or less than 92.4Vac, NTU-1200-124 will enter Charger the inverter mode to keep equipment running, and the energy is consumed from the battery. (Suggest to work accompany with MEAN WELL NPB/NPP chargers)
After the fault condition When connecting the DC polarity reversely, the internal fuse will blow for is remove, re-power inverter for Load protection. The unit then must return to MEAN WELL's distributor for further operation. support. Low DC Input Protection :...
※ MEAN WELL posses the right to adjust the content of this manual. Please refer to the latest version of our manual on our website. https://www.meanwell.com...
Page 26
N o . 2 8 , W u q u a n 3 r d R d . , W u g u D i s t . , N e w Ta i p e i C i t y 2 4 8 , Ta i w a n...