24
Info
Too long start-up of a function
28
Info
Slave device connected
31
Failure in de-icing
41
Frost protection hot water tank
active
44
Failure on anode in domestic hot
water tank
45
Info
Start anti legionella
46
Failure in anti legionella function
47
Heat pump de-icing failure
49
Compressor high pressure alarm
62
Database error
65
Changed type of slave device
69
Leaking brine circuit BAH solution
75
Sensor fault
80
Too low temperature in the
evaporator
81
Info
Electric supplement heater in hot
water tank is on
82
Info
Electric supplement heater in hot
water tank is off
85
Slave SW not the same as master
86
Slave RTDB not the same as master
Compact P / Compact P Polar (English)
Software error
A new slave device has been
connected
De-icing error (2 hours)
Frost protection of DHW hot water
tank has been active
Error in the DHW hot water tank
anode
Anti legionella function for DHW hot
water tank has started
The anti-legionella function in the
DHW hot water tank could not be
completed after 20 attempts, or the
maximum period of 5 hours has
passed
Error on heat pump de-icing
Compressor is showing a high
pressure alarm
Type of slave device has been
changed
There is a leak in the brine circuit of
the BAH solution
There is an error on one or more
sensors
The evaporater element has been
too cold (<-20 °C)
Electric supplement heater in the
DHW tank has been turned on
Electric supplement heater in the
DHW tank has been turned off
Software version for slave unit is
not the same as on the master
Slave RTDB version is not the same
as master
BY NILAN
Turn the unit off and on again.
If the error reoccurs, contact the
installer.
Check counterflow heat exchanger.
If necessary, remove and thaw
under a shower.
Replace anode and check anode
monitoring.
Adjust time before startup to e.g.
night so there is enough time to
restart the anti-legionella function.
Check that T6 de-icing has been
activated.
Check that there is sufficient
airflow over the condenser and
water in the hot water tank.
Check that the outdoor air
temperature is not over 45°C.
Contact installer.
Check dip-switch settings.
Repair the brine circuit on the BAH
solution.
Check the sensors by reading off
data under Information.
Check airflow over the evaporator.
Check that the filters are clean and
there is free passage in the air
intake.
Update software so that both are
running the same version.
Update software so that both are
running the same version.